Potentiometer Settings

Input Range Settings – The parameters in the following table adjust the input
characteristics of the integrated potentiometer. When using the potentiometer to
command the inverter output frequency, these parameters adjust the starting and
ending ranges for the potentiometer, as well as the output frequency range.

“A” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

Pot. input active range start
frequency

A151

POT-EXS

0000.0Hz

The output frequency
corresponding to the pot. range
starting point,
range is 0.0 to 400.0 Hz

U

0.0

0.0

Hz

Pot. input active range end
frequency

A152

POT-EXE

0000.0Hz

The output frequency
corresponding to the pot. range
ending point,
range is 0.0 to 400.0 Hz

U

0.0

0.0

Hz

Pot. input active range start

A153

POT-EX%S

00000%

The starting point (offset) for the
potentiometer range,
range is 0. to 100.%

U

0.

0.

%

Pot. input active range end

A154

POT-EX%E

00000%

The ending point (offset) for the
potentiometer range,
range is 0. to 100.%

U

100.

100.

%

Pot. input start frequency
enable

A155

POT-LVL

0Hz

Two options; select codes:
00

}Use offset (A151 value)

01

}Use 0Hz

U

01

01



Max frequency

A152

A151

A154

100%

Counterclockwise

Clockwise

A153

0%

A015=00

A015=01

0

Input scale

%

3

31

Config

uri
ng Driv

e

Parameters

3

−31

&RQ¿JXULQJ'ULYH

Parameters