Two Stage Acceleration and Deceleration

When terminal [2CH] is turned ON, the
inverter changes the rate of acceleration and
deceleration from the initial settings (F002
and F003) to use the second set of
acceleration/ deceleration values. When the
terminal is turned OFF, the inverter is
returned to the original acceleration and
deceleration time (F002 acceleration time 1,
and F003 deceleration time 1). Use A092
(acceleration time 2) and A0093 (deceleration
time 2) to set the second stage acceleration
and deceleration times.

In the graph shown above, the [2CH] becomes active during the initial acceleration.
This causes the inverter to switch from using acceleration 1 (F002) to acceleration 2
(A092).

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

Frequency output uses 2nd-stage acceleration and
deceleration values

09

2CH

Two-stage Accelera-
tion and Deceleration

OFF

Frequency output uses the initial acceleration 1
and deceleration 1 values

Valid for inputs:

C001~C005

Required settings

A092, A093, A094=00

Notes:
x Function A094 selects the method for second

stage acceleration. It must be set = 00 to select
the input terminal method in order for the
[2CH] terminal assignment to operate.

Example (default input configuration shown—see

page 3–49

):

See I/O specs on

page 4–6.

5

4

3

2

1

L PCS P24

2CH

- FU models

[2CH]

1

0

Output
frequency

t

[FW,RV]

1

0

Target
frequency

initial

second

4

17

Operations and

Monitori

ng

4

−17

Operations and

Monitoring