F” group: main profile parameters -9, F” group: main profile parameters – XLT Hitachi X200 User Manual

Page 92

Advertising
background image

“F” Group: Main Profile Parameters

The basic frequency (speed) profile is
defined by parameters contained in the “F”
Group as shown to the right. The set
running frequency is in Hz, but acceleration
and deceleration are specified in the time
duration of the ramp (from zero to
maximum frequency, or from maximum
frequency to zero). The motor direction
parameter determines whether the keypad
Run key produces a FWD or REV command.
This parameter does not affect the
intelligent terminal [FW] and [REV]
functions, which you configure separately.

Acceleration 1 and Deceleration 1 are the standard default accel and decel values for the
main profile. Accel and decel values for an alternative profile are specified by using
parameters Ax92 through Ax93. The motor direction selection (F004) determines the
direction of rotation as commanded only from the keypad. This setting applies to any
motor profile (1st or 2nd) in use at t particular time.

“D” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

Output frequency setting

F001

VR

0000.0Hz

Standard default target
frequency that determines
constant motor speed, range is
0.0 / start frequency to 400 Hz

9

0.0

0.0

Hz

Acceleration (1) time setting

F002

ACC 1

010.00s

Standard default acceleration,
range is 0.01 to 3000 sec.

9

10.0

10.0

sec.

Acceleration (1) time setting,
2nd motor

F202

2ACC 1

010.00s

Standard default acceleration,
2nd motor
range is 0.01 to 3000 sec.

9

10.0

10.0

sec.

Deceleration (1) time setting

F003

DEC 1

010.00s

Standard default deceleration,
range is 0.01 to 3000 sec.

9

10.0

10.0

sec.

Deceleration (1) time setting,
2nd motor

F203

2DEC 1

010.00s

Standard default deceleration,
2nd motor
range is 0.01 to 3000 sec.

9

10.0

10.0

sec.

Cumulative power-on time
monitor

F004

DIG-RUN

FWD

Two options; select codes:
00

}Forward

01

}Reverse

U

00

00



Output
frequency

0

t

F001

F002

F003

3

9

Config

uri
ng Driv

e

Parameters

3

−9

&RQ¿JXULQJ'ULYH

Parameters