Network Detection Signal (FieldBus Option)

The Network Detection Signal output indicates the general status of network
communications when using a FieldBus option. The inverter has a programmable
watchdog timer to monitor network activity. Parameter P044 sets the time-out period. If
communications stop or pause longer than the specified time-out period, the ODc output
turns ON.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

when the communication watchdog timer (period
specified by P044) has timed out.

10

ODc

Network
Disconnection
Signal
(Option module)

OFF

when the communication watchdog timer is
satisfied by regular communications activity

Valid for inputs:

11, AL0 – AL2

Required settings

P044, P045

Notes:

x To disable the communications watchdog timer,

set P044=00.00 sec.

Example for terminal [11] (default output
configuration shown – see

page 3-54

):

Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see

page 4-35 and 3-54

):

See I/O specs on

page 4-6

RY

Inverter output
terminal circuit

CM2

11

ODc

AL1

Power
supply

Load

AL0

AL2

Inverter logic
circuit board

ODc

4

53