General Inverter Electrical Measurements

The following table specifies how to measure key system electrical parameters. The
diagrams on the next page show inverter-motor systems and the location of
measurement points for these parameters.

Parameter

Circuit location of

measurement

Measuring

instrument

Notes

Reference Value

Supply voltage

E

1

E

R

– across L1 and L2

E

S

– across L2 and L3

E

T

– across L3 and L1

Fundamental
wave effective
value

Commercial supply
voltage
200V class:
200–240V, 50/60 Hz
400V class:
380–460V, 50/60 Hz

Supply current

I

1

I

r

– L1

I

s

– L2

I

t

– L3

Total effective
value

Supply power

W

1

W

11

– across L1 and L2

W

12

– across L2 and L3

Moving-coil type
voltmeter or
rectifier type
voltmeter

Total effective
value

Supply power

factor Pf

1

%

100

3

1

1

1

1

u

u

u

I

E

W

Pf

Output voltage

E

O

E

U

– across U and V

E

V

– across V and W

E

W

– across W and U

Rectifier type
voltmeter

Total effective
value

Output current

I

O

I

U

– U

I

V

– V

I

W

– W

Moving-coil type
ammeter

Total effective
value

Output power

W

O

W

O1

– across U and V

W

O2

– across V and W

Electronic type
wattmeter

Total effective
value

Output power

factor Pf

O

Calculate the output power factor from the output voltage E,
output current I, and output power W.

%

100

3

1

u

u

u

O

O

O

I

E

W

Pf

Note 1:

Use a meter indicating a fundamental wave effective value for voltage, and meters
indicating total effective values for current and power.

Note 2:

The inverter output has a distorted waveform, and low frequencies may cause
erroneous readings. However, the measuring instruments and methods listed above
provide comparably accurate results.

Note 3:

A general-purpose digital volt meter (DVM) is not usually suitable to measure a
distorted waveform (not pure sinusoid).