Pid loop operation -58, Pid loop operation – XLT Hitachi X200 User Manual

Page 207

Advertising
background image

PID Loop Operation

In standard operation, the inverter uses a reference source selected by parameter A001
for the output frequency, which may be a fixed value (F001), a variable set by the front
panel potentiometer, or value from an analog input (voltage or current). To enable PID
operation, set A071=01. This causes the inverter to

calculate

the target freq, or setpoint.

A calculated target frequency can have a lot of advantages. It lets the inverter adjust
the motor speed to optimize some other process of interest, potentially saving energy as
well. Refer to the figure below. The motor acts upon the external process. To control that
external process, the inverter must monitor the process variable. This requires wiring a
sensor to either the analog input terminal [O] (voltage) or terminal [OI] (current).

When enabled, the PID loop calculates the ideal output frequency to minimize the loop
error. This means we no longer command the inverter to run at a particular frequency,
but we specify the ideal value for the process variable. That ideal value is called the

setpoint

, and is specified in the units of the external process variable. For a pump

application it may be gallons/minute, or it could be air velocity or temperature for an
HVAC unit. Parameter A075 is a scale factor that relates the external process variable
units to motor frequency. The figure below is a more detailed diagram of the function.

NOTE: You cannot use [O] and [OI] simultaneously. For example, if you select [OI] for
the setpoint, it is not possible to use [O] for the Process Variable, and vice versa.

Setpoint

(Target)

Scale factor

Reciprocal

Standard setting

Multi-speed

settings

to

Potentiometer on

keypad

F001

A020

A035

Frequency

source select

A001

V/I input

select

[AT]

O

OI

L

A076 PID V/I input select

Voltage

Current

+

SP

A075

1

A072

P gain

A073

I gain

A074

D gain

+

Frequency

setting

A072

Scale factor

F001

Process Variable (Feedback)

Analog input scaling

A015

A013

A014

A011

A012

A GND

A075

Scale factor

D004

Monitor

Setpoint

SP

+

PID

Calculation

Error

Freq.

Inverter

Motor

External
Process

Sensor

Process Variable (PV)

PV

4

58

Inverter Mounting

and i

n

st

all

ation

4

−58

Operations and

Monitoring