B−27, B 27 – XLT Hitachi X200 User Manual

Page 270

Advertising
background image

List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

A051

DC braking enable

R/W Two options; select codes:

00...Disable
01... Enable
02... Frequency detection

1051h

0, 1, 2



A052

DC braking frequency
setting

R/W The frequency at which DC

braking begins, range is from the
start frequency (B082) to 60 Hz

1052h (B082 x 10)

to 600

0.1 Hz

A053

DC braking wait time

R/W The delay from the end of

controlled deceleration to start of
DC braking (motor free runs
until DC braking begins),
range is 0.0 to 5.0 sec.

1053h

0 to 50



A054

DC braking force for
deceleration

R/W Level of DC braking force,

settable from 0 to 100%

1054h

0 to 100

1 %

A055

DC braking time for
deceleration

R/W Sets the duration for DC

braking, range is 0.0 to 60.0
seconds

1055h

0 to 600

0.1 sec

A056

DC braking / edge or
level detection for [DB]
input

R/W Two options; select codes:

00... Edge detection
01... Level detection

1056h

0, 1



A061

Frequency upper limit
setting

R/W Sets a limit on output frequency

less than the maximum
frequency (A004). Range is from
frequency lower limit (A062) to
maximum frequency (A004).
0.0.. setting is disabled
>0.1 setting is enabled

105Ah (A062 x 10)

to (A004 x

10),

0=disable

>1=enable

A261

Frequency upper limit
setting, 2nd motor

R/W Sets a limit on output frequency

less than the maximum
frequency (A204). Range is from
frequency lower limit (A262) to
maximum frequency (A204).
0.0.. setting is disabled
>0.1 setting is enabled

1517h

(A262 x 10)

to (A204 x

10),

0=disable

>1=enable

0.1 Hz

A062

Frequency lower limit
setting

R/W Sets a limit on output frequency

greater than zero.
Range is start frequency (B082)
to frequency upper limit (A061)
0.0 setting is disabled
>0.0 setting is enabled

105Bh (B082 x 10)

to (A061 x

10),

0=disable

>1=enable

A262

Frequency lower limit
setting, 2nd motor

R/W Sets a limit on output frequency

greater than zero.
Range is start frequency (B082)
to frequency upper limit (A261)
0.0 setting is disabled
>0.0 setting is enabled

1518h

(B082 x 10)

to (A261 x

10),

0=disable

>1=enable

0.1 Hz

A063,
A065,

A067

Jump (center)
frequency setting

R/W Up to 3 output frequencies can be

defined for the output to jump
past to avoid motor resonances
(center frequency)
Range is 0.0 to 400.0 Hz

105Dh

1060h
1063h

0 to 4000

0.1 Hz

A064,
A066,

A068

Jump (hysteresis)
frequency width
setting

R/W Defines the distance from the

center frequency at which the
jump around occurs
Range is 0.0 to 10.0 Hz

105Eh

1061h
1064h

0 to 100

0.1 Hz

B

27

Appe

ndix B

B

−27

Appendix B

Advertising