Multi-Speed Select

The inverter can store up to 16 different target
frequencies (speeds) that the motor output uses for
steady-state run condition. These speeds are
accessible through programming five of the intelligent
terminals as binary-encoded inputs CF1 to CF4 per
the table to the right. These can be any of the six
inputs, and in any order. You can use fewer inputs if
you need eight or fewer speeds.

NOTE: When choosing a subset of speeds to use,
always start at the top of the table, and with the
least-significant bit: CF1, CF2, etc.

The example with eight speeds in the
figure below shows how input switches
configured for CF1–CF3 functions can
change the motor speed in real time.

NOTE: Speed 0 is set by the A020
parameter value.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

Binary encoded speed select, Bit 0, logical 1

02

CF1

Multi-speed Select,
Bit 0 (LSB)

OFF

Binary encoded speed select, Bit 0, logical 0

ON

Binary encoded speed select, Bit 1, logical 1

03

CF2

Multi-speed Select,
Bit 1

OFF

Binary encoded speed select, Bit 1, logical 0

ON

Binary encoded speed select, Bit 2, logical 1

04

CF3

Multi-speed Select,
Bit 2

OFF

Binary encoded speed select, Bit 2, logical 0

ON

Binary encoded speed select, Bit 3, logical 1

05

CF4

Multi-speed Select,
Bit 3 (MSB)

OFF

Binary encoded speed select, Bit 3, logical 0

Valid for inputs:

C001~C005

Required settings

F001, A001=02,
A020 to A035

Notes:
x When programming the multi-speed settings, be

sure to press the Store key each time and then
set the next multi-speed setting. Note that when
the key is not pressed, no data will be set.

x When a multi-speed setting more than 50Hz

(60Hz) is to be set, it is necessary to program the
maximum frequency A004 high enough to allow
that speed

Example (some CF inputs require input
configuration; some are default inputs—see

page 3–

49

):

See I/O specs on

page 4–6.

Multi-

speed

Input Function

CF4 CF3 CF2 CF1

Speed 0

0

0

0

0

Speed 1

0

0

0

1

Speed 2

0

0

1

0

Speed 3

0

0

1

1

Speed 4

0

1

0

0

Speed 5

0

1

0

1

Speed 6

0

1

1

0

Speed 7

0

1

1

1

Speed 8

1

0

0

0

Speed 9

1

0

0

1

Speed 10

1

0

1

0

Speed 11

1

0

1

1

Speed 12

1

1

0

0

Speed 13

1

1

0

1

Speed 14

1

1

1

0

Speed 15

1

1

1

1

Speed

0th

4th

6th

1st

2nd

5th

7th

3rd

1
0
1
0

1
0

1
0

[CF1]

[CF2]

[CF3]

[FW]

5

4

3

2

1

L PCS P24

CF1

CF2

CF3

CF4

4

12

Operations and

Monitori

ng

4

−12

Operations and

Monitoring