XLT Hitachi X200 User Manual

Page 199

Advertising
background image

Network Detection Signal (Integrated ModBus)

The Network Detection Signal output indicates the general status of network
communications (integrated ModBus communication). The inverter has a
programmable watchdog timer to monitor network activity. Parameter C077 sets the
time-out period. If communications stop or pause longer than the specified time-out
period, the NDc output turns ON.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

when the communication watchdog timer (period
specified by C077) has timed out.

08

NDc

Network
Disconnection
Signal (ModBus)

OFF

when the communication watchdog timer is
satisfied by regular communications activity

Valid for inputs:

11, AL0 – AL2

Required settings

C076, C077

Notes:

x To disable the communications watchdog timer,

set C077=00.00 sec.

x If you set Communications Error Select to

“Disable” (C076=02), you still have the option of
using the Network Detection Signal and setting
the watchdog time-out period with C077.

Example for terminal [11] (default output
configuration shown – see

page 3-54

):

Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see

page 4-35 and 3-54

):

See I/O specs on

page 4-6

Additionally, the inverter can respond to a communications time-out in various ways.
Refer to the following diagram (top of next page). You configure the desired response via
function C076, Communications Error Select. This selects whether or not you want the
inverter to trip (alarm with error code E60) and whether to stop the motor or just let it
coast. Together, parameters C076 and C077 set the network detection watchdog time-
out and the inverter’s response.

RY

Inverter output
terminal circuit

CM2

11

NDc

AL1

Power
supply

Load

AL0

AL2

Inverter logic
circuit board

NDc

4

50

Inverter Mounting

and i

n

st

all

ation

4

−50

Operations and

Monitoring

Advertising