Local Monitoring During Network Operation

The X200 inverter’s serial port may be connected to a network or to an external digital
operator. During those times, the inverter keypad keys will not function (except for the
Stop key). However, the inverter’s 4-digit display still provides the Monitor Mode
function, displaying any of the parameters D001 to D007. Function B089, Monitor
Display Select for Networked Inverter, determines the particular D00x parameter
displayed. Refer to table below.

B089 Monitor Display Select for Networked Inverter

Option

Code

Monitor

Code

Monitor Function Name

01

D001

Output frequency monitor

02

D002

Output current monitor

03

D003

Rotation direction monitor

04

D004

Process variable (PV),PID feedback monitor

05

D005

Intelligent input terminal status

06

D006

Intelligent output terminal status

07

D007

Scaled output frequency monitor

When monitoring the inverter during network operation, please note the following:

x The inverter display will monitor D00x functions according to B089 setting when…

¾ The OPE/485 DIP switch is set to the “485” position, or
¾ A device is already connected to the inverter’s serial port at inverter powerup.

x During network operation, the inverter keypad will also display error codes for

inverter trip events. Use the Stop key or inverter Reset function to clear the error.
Refer to “

Error Codes

” on page 6-5 to interpret the error codes.

x The Stop key can be disabled, if you prefer, by using function B087.

3

8

Config

uri

ng Driv

e

Parameters

3

−8

&RQ¿JXULQJ'ULYH

Parameters