Forward Run/Stop and Reverse Run/Stop Commands:

When you input the Run command via the terminal [FW], the inverter executes the
Forward Run command (high) or Stop command (low). When you input the Run
command via the terminal [RV], the inverter executes the Reverse Run command (high)
or Stop command (low).

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

Inverter is in Run Mode, motor runs forward

00

FW

Forward Run/Stop

OFF

Inverter is in Stop Mode, motor stops

ON

Inverter is in Run Mode, motor runs reverse

01

RV

Reverse Run/Stop

OFF

Inverter is in Stop Mode, motor stops

Valid for inputs:

C001~C005

Required settings

A002 = 01

Notes:
x When the Forward Run and Reverse Run

commands are active at the same time, the
inverter enters the Stop Mode.

x When a terminal associated with either [FW]

or [RV] function is configured for

normally

closed, the motor starts rotation when that
terminal is disconnected or otherwise has no
input voltage.

Example (default input configuration shown

– see

page 3-49

)

See I/O specs on

page 4-6

.

NOTE: The parameter F004, Keypad Run Key Routing, determines whether the single
Run key issues a Run FWD command or Run REV command. However, it has no effect
on the [FW] and [RV] input terminal operation.

WARNING: If the power is turned ON and the Run command is already active, the
motor starts rotation and is dangerous! Before turning power ON, confirm that the Run
command is not active.

5

4

3

2

1

L PCS P24

FW

RV

4

11

Operations and

Monitori

ng

4

−11

Operations and

Monitoring