Second Acceleration and Deceleration Functions

The X200 inverter features two-stage acceleration and deceleration ramps. This gives
flexibility in the profile shape. You can specify the frequency transition point, the point
at which the standard acceleration (F002) or deceleration (F003) changes to the second
acceleration (A092) or deceleration (A093). Or, you can use intelligent input [2CH] to
trigger this transition. These profile options are also available for the second motor
settings. Select a transition method via A094 as depicted below. Be careful not to
confuse the

second acceleration/deceleration settings

with settings for the

second motor

!

“A” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

Acceleration (2) time setting

A092

ACC 2

0015.00s

Duration of 2nd segment of
acceleration, range is:
0.01 to 3000 sec.

9

15.00 15.00

sec

Acceleration (2) time setting,
2nd motor

A292

2ACC2

0015.00s

Duration of 2nd segment of
acceleration, 2nd motor, range is:
0.01 to 3000 sec.

9

15.00 15.00

sec

Deceleration (2) time setting

A093

DEC 2

0015.00s

Duration of 2nd segment of
deceleration, range is:
0.01 to 3000 sec.

9

15.00 15.00

sec

Deceleration (2) time setting,
2nd motor

A293

2DEC2

0015.00s

Duration of 2nd segment of
deceleration, 2nd motor, range is:
0.01 to 3000 sec.

9

15.00 15.00

sec

Select method to switch to
Acc2/Dec2 profile

A094

ACC CHG

TM

Two options for switching from
1st to 2nd accel/decel:
00

}2CH input from terminal

01

}Transition frequency

U

00

00



Select method to switch to
Acc2/Dec2 profile, 2nd motor

A294

2ACCCHG

TM

Two options for switching from
1st to 2nd accel/decel:
00

}2CH input from terminal

01

}Transition frequency

(2nd motor)

U

00

00



A094 = 00

Transition via 2CH input

Output
frequency

Accel 1

Accel 2

2CH
input

1

0

t

t

0

A094 = 01

Transition via freq. level

Output
frequency

Accel 1

Accel 2

t

0

A095

Frequency
transition point

3