XLT Hitachi X200 User Manual

Page 188

Advertising
background image

Run Signal

When the [RUN] signal is selected as an
intelligent output terminal, the inverter
outputs a signal on that terminal when
it is in Run Mode. The output logic is
active low, and is the open collector type
(switch to ground).

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

when inverter is in Run Mode

00

RUN

Run Signal

OFF

when inverter is in Stop Mode

Valid for inputs:

11, AL0 – AL2

Required settings

(none)

Notes:

x The inverter outputs the [RUN] signal

whenever the inverter output exceeds the start
frequency specified by parameter B082

. The

start frequency is the initial inverter output
frequency when it turns ON.

x The example circuit for terminal [11] drives a

relay coil. Note the use of a diode to prevent the
negative going turn-off spike generated by the
coil from damaging the inverter’s output
transistor.

Example for terminal [11] (default output
configuration shown – see

page 3-54

):

Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see

page 4-35 and 3-54

):

See I/O specs on

page 4-6

RY

Inverter output
terminal circuit

CM2

11

RUN

AL1

Power
supply

Load

AL0

AL2

Inverter logic
circuit board

RUN

[FW,RV]

1

0

Output
frequency

t

Run
signal

1

0

start freq.

B082

ON

4

39

Operations and

Monitori

ng

4

−39

Operations and

Monitoring