It is possible for the inverter to retain the frequency set from the [UP] and [DWN]
terminals through a power loss. Parameter C101 enables/disables the memory. If
disabled, the inverter retains the last frequency before an UP/DWN adjustment. Use
the [UDC] terminal to clear the memory and return to the original set output frequency.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

Accelerates (increases output frequency) motor
from current frequency

27

UP

Remote Control UP
Function (motorized
speed pot.)

OFF

Output to motor operates normally

ON

Decelerates (increases output frequency) motor
from current frequency

28

DWN

Remote Control
DOWN Function
(motorized speed pot.)

OFF

Output to motor operates normally

ON

Clears the Up/Down frequency memory

29

UDC

Remote Control Data
Clear

OFF

No effect on Up/Down memory

Valid for inputs:

C001~C005

Required settings

A001 = 02

Notes:

x This feature is available only when the frequency

command source is programmed for operator
control. Confirm A001 is set to 02.

x This function is not available when [JG] is in use.

x The range of output frequency is 0 Hz to the value

in A004 (maximum frequency setting).

Example (default input configuration shown—see

page 3–49

):

See I/O specs on

page 4–6.

x The minimum ON time of [UP] and [DWN] is 50 ms.

x This setting modifies the inverter speed from using F001 output frequency setting as a starting point.

5

4

3

2

1

L PCS P24

UP

DWN

4

28

4

−28