Overload restriction, Frequency pull-in restart – XLT Hitachi X200 User Manual

Page 118

Advertising
background image

Overload Restriction

If the inverter’s output current exceeds a
preset current level you specify during
acceleration or constant speed, the overload
restriction feature automatically reduces the
output frequency to restrict the overload.
This feature does not generate an alarm or
trip event. You can instruct the inverter to
apply overload restriction only during
constant speed, thus allowing higher
currents for acceleration. Or, you may use
the same threshold for both acceleration and
constant speed.

When the inverter detects an overload, it
must decelerate the motor to reduce the
current until it s less than the threshold. You
can choose the rate of deceleration that the
inverter uses to lower the output current.

“B” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

Overload restriction
operation mode

B021

OL Mode

ON

U

01

01



Overload restriction
operation mode, 2nd motor

B221

2OL Mode

ON

Select the operation mode during
overload conditions, three
options, option codes:
00

}Disabled

01

}Enabled for acceleration and

constant speed

02

}Enabled for constant speed

only

U

01

01



Overload restriction level
setting

B022

OL LVL

002.40A

U

Rated

current

x 1.5

A

Overload restriction level
setting, 2nd motor

B222

2OL LVL

002.40A

Sets the level for overload
restriction, between 20% and
150% of the rated current of the
inverter, setting resolution is 1%
of rated current

U

Rated

current

x 1.5

A

Deceleration rate at overload
restriction

B023

OL Cnst

0001.0s

U

1.0

30.0

sec.

Deceleration rate at overload
restriction, 2nd motor

B223

2OL Cnst

0001.0s

Sets the deceleration rate when
inverter detects overload, range
is 0.1 to 30.0, resolution 0.1

U

1.0

30.0

sec.

Source of overload restriction
selection

B028

OL L_SLCT

PARAM

Two option codes:
00

}set value of B022

01

}[O] input

U

00

00



Source of overload restriction
selection, 2nd motor

B228

2OL L_SLCT

PARAM

Two option codes:
00

}set value of B222

01

}[O] input

U

00

00



Frequency Pull-in Restart

See “

Restart Mode Configuration

” (B088) section on page 3-42

.

Motor
current

Restriction area

B022

0

t

Output
frequency

0

t

B022

3

35

Config

uri
ng Driv

e

Parameters

3

−35

&RQ¿JXULQJ'ULYH

Parameters