No response occurs:

In the cases below, the inverter ignores a query and returns no response.

x When receiving a broadcasting query

x When detecting a transmission error in reception of a query

x When the slave address set in the query is not equal to the slave address of the

inverter

x When a time interval between data elements constituting a message is shorter than

3.5 characters

x When the data length of the query is invalid

NOTE: Provide a timer in the master and make the master retransmit the same query
when no response is made within a preset time period after the preceding query was
sent.