Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 102

Advertising
background image

3-48

Programming and Parameters

369

Brake OL Cnfg

Enter a value to configure the drive's response to a Brake Overload (OL) Trip exception
event. This event is triggered when a Dynamic Brake (DB) overload condition occurs.

• 0 “Ignore” - Configures the drive to continue running, as normal, when this event

occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the

appropriate fault bit, in response this event

• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the

appropriate fault bit, in response this event

Default:
Options:

0
0
1
2
3

“Alarm”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”

370

HiHp InPhsLs Cfg

Selector for the input phase loss configuration.

• 0 “Ignore” - Configures the drive to continue running, as normal, when this event

occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the

appropriate fault bit, in response this event

• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the

appropriate fault bit, in response this event

Default
Options:

1
0
1
2
3
4

“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”

371

Mtr OL Trip Cnfg

Enter a value to configure the drive's response to a Motor Overload (OL) Trip exception
event.

• 0 “Ignore” - Configures the drive to continue running, as normal, when this event

occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the

appropriate fault bit, in response this event

• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the

appropriate fault bit, in response this event

Default:
Options:

2
0
1
2
3
4

“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”

372

Mtr OL Pend Cnfg

Enter a value to configure the drive's response to a Motor Overload (OL) Pending
exception event.

• 0 “Ignore” - Configures the drive to continue running, as normal, when this event

occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the

appropriate fault bit, in response this event

• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the

appropriate fault bit, in response this event

Default:
Options:

1
0
1
2
3
4

“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”

373

Motor Stall Time

Enter a value to specify the time delay between when the drive detects a Motor Stall
condition and when it declares the exception event.

Units:
Default:
Min/Max:

Sec
1.0000
0.1000/3000.0000

✓ ✓ Real

374

Motor Stall Cnfg

Enter a value to configure the drive's response to a Motor Stall exception event.

• 0 “Ignore” - Configures the drive to continue running, as normal, when this event

occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the

appropriate fault bit, in response this event

• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the

appropriate fault bit, in response this event

Default:
Options:

0
0
1
2
3
4

“Ignore”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”