Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 176

Advertising
background image

A-12

Supplemental Information

480 Volt AC Input Frames 9…11 Drive Protection Devices

600 Volt AC Input Frames 1…6 Drive Protection Devices

Drive Catalog

Number

Fr

am

e

HP Rating

Input

Ratings

Dual Element Time Delay Fuse

Non-Time Delay Fuse

Bussmann Style Semi-

Conductor Fuse

Circuit

Breaker

(3)

Motor Circuit

Protector

(5)

ND

HD

Amps

Min.

(1)

Max.

(2)

Min.

(1)

Max.

(3)

Max.

(4)

Max.

(5)

20DD261

9

200

-

252

350

550

350

700

170M5813

700

400

-

150

207

275

450

275

600

170M5813

600

300

20DD300

9

250

-

290

400

650

400

900

170M5813

900

400

-

200

247

350

550

350

700

170M5813

700

400

20DD385

10

300

-

372

500

850

500

1100

170M5813

1100

600

-

250

302

400

650

400

900

170M5813

900

400

20DD460

10

350

-

444

600

1000

600

1300

170M8547

1300

600

-

300

388

500

850

500

1100

170M8547

1100

600

20DD500

10

450

-

483

650

1000

650

1500

170M8547

1500

700

-

350

423

550

900

550

1200

170M8547

1200

600

20DD590

11

500

-

570

750

(1 per phs)

375

(2 per phs)

1300

750

(1 per phs)

375

(2 per phs)

1700

170M5813

1700

800

-

450

524

700

(1 per phs)

350

(2 per phs)

1100

700

(1 per phs)

350

(2 per phs)

1500

170M5813

1500

700

20DD650

11

500

-

628

800

(1 per phs)

400

(2 per phs)

1400

800

(1 per phs)

400

(2 per phs)

1900

170M5813

1900

800

-

500

594

750

(1 per phs)

375

(2 per phs)

1300

750

(1 per phs)

375

(2 per phs)

1700

170M5813

1700

800

20DD730

11

600

-

705

900

(1 per phs)

450

(2 per phs)

1600

900

(1 per phs)

450

(2 per phs)

2100

170M5813

2100

900

-

500

655

850 (1 per phs)
425 (2 per phs)

1400

850

(1 per phs)

425

(2 per phs)

1900

170M5813

1900

900

(1)

Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.

(2)

Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(3)

Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(4)

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

(5)

Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.

Drive

Catalog

Number

Fr

am

e

HP Rating

Input Ratings Dual Element

Time Delay Fuse

Non-Time Delay

Fuse

Circuit

Breaker

(3)

Motor

Circuit

Protector

(5)

140M Motor Starter with Adjustable Current Range

(6)(7)

ND

HD

Amps

kVA

Min.

(1)

Max.

(2)

Min.

(3)

Max.

(4)

Max.

(4)

Max.

(6)

Available Catalog Numbers

(8)

Minimum Enclosure
Volume (in.

3

)

(9)

20DE1P7

1

1

0.75

1.3

1.4

2

4

2

6

15

3

M-C2E-B16

7269

20DE2P7

1

2

1.5

2.1

2.1

3

6

3

10

15

3

M-C2E-B25

7269

20DE3P9

1

3

2

3.0

3.1

6

9

6

15

15

7

M-C2E-B40

M-D8E-B40

7269

20DE6P1

1

5

3

5.3

5.5

9

12

9

20

20

15

M-D8E-B63

7269

20DE9P0

1

7.5

5

7.8

8.1

10

20

10

35

30

15

M-D8E-C10

M-F8E-C10

7269

20DE011

1

10

7.5

9.9

10.2

15

25

15

40

40

15

M-D8E-C10

M-F8E-C10

7269

20DE017

1

15

10

15.4

16.0

20

40

20

60

50

20

M-D8E-C16

M-F8E-C16

7269

20DE022

2

20

15

20.2

21.0

30

50

30

80

80

30

M-F8E-C25

7269

20DE027

2

25

20

24.8

25.7

35

60

35

100

100

50

M-F8E-C25

7269

20DE032

3

30

25

29.4

30.5

40

70

40

125

125

50

M-F8E-C32

13630

20DE041

3

40

30

37.6

39.1

50

90

50

150

150

100

20DE052

3

50

40

47.7

49.6

60

110

60

200

200

100

20DE062

4

60

50

58.2

60.5

80

125

80

225

225

100

20DE077

5

75

72.3

75.1

90

150

90

300

300

100

60

58.2

60.5

90

125

90

250

250

100