3-42

Programming and Parameters

304

Limit Status

Displays the limit status of conditions that may be limiting the current reference or torque reference.

• Bit 0 [+MCS Iq Lim] indicates that torque producing current is at its positive limit.

• Bit 1 [+MCS Ws Lim] indicates that flux producing torque is at its positive limit.

• Bit 2 [0 Ia from +] indicates that torque producing current is limited to zero from the positive direction - refer to Par 353 [Iq Actual Lim].

• Bit 3 [+Iq Calc] indicates the calculation for torque producing current has reached its positive limit.

• Bit 4 [+Current Lim] indicates that the current reference has reached the positive Motor Current Limit set by Par 356 [Mtr Current Lim].

• Bit 5 [+DriveProtOL] indicates that the current reference has reached the positive current limit set by the Open Loop Inverter Overload, shown in Par 343 [OL

OpnLp CurrLim].

• Bit 6 [+DriveProtCL] indicates that the current reference has reached the positive current limit set by the Closed Loop Inverter Overload, shown in Par 344

[OL ClsLp CurrLim].

• Bit 8 [+Torq Limit] indicates that the torque reference has reached the Positive Torque Limit set by Par 125 [Torque Pos Limit].

• Bit 9 [Mtrng PwrLim] indicates that the torque reference is being limited by the Motoring Power Limit set by Par 127 [Mtring Power Lim].

• Bit 10 [+Torq CurLim] indicates that current reference has reached the Actual Torque Producing Current Limit set by Par 353 [Iq Actual Lim].

• Bit 11 [Atune Tq Lim] indicates that the torque reference is being limited by Par 129 [Atune Torq Ref].

• Bit 12 [+0 Torq Ena] indicates that the torque reference is limited to zero because Par 157 [Logic Ctrl State] bit 9 [Torq Ref En] is off.

• Bit 13 [+0 Curr Ena] indicates that the current reference is limited to zero because Par 157 [Logic Ctrl State] bit 11 [CurrRef En] is off.

• Bit 16 [-MCS Iq Lim] indicates that torque producing current is at its negative limit.

• Bit 17 [-MCS Ws Lim] indicates that flux producing torque is at its negative limit.

• Bit 18 [0 Iq from -] indicates that torque producing current is limited to zero from the negative direction - refer to Par 353 [Iq Actual Lim].1

• Bit 19 [-Iq Calc] indicates the calculation for torque producing current has reached its negative limit.

• Bit 20 [-Current Lim] indicates that the current reference has reached the negative Motor Current Limit set by Par 356 [Mtr Current Lim].

• Bit 21 [-DriveProtOL] indicates that the current reference has reached the negative current limit set by the Open Loop Inverter Overload, shown in Par 343

[OL OpnLp CurrLim].

• Bit 22 [-DriveProtCL] indicates that the current reference has reached the negative current limit set by the Closed Loop Inverter Overload, shown in Par 344

[OL ClsLp CurrLim].

• Bit 24 [-Torq Limit] indicates that the torque reference has reached the Negative Torque Limit set by Par 126 [Torque Neg Limit].

• Bit 25 [Regen PwrLim] indicates that the torque reference is being limited by the Regenerative Power Limit set by Par 128 [Regen Power Lim].

• Bit 26 [-Torq CurLim] indicates that current reference has reached the Actual Torque Producing Current Limit set by Par 353 [Iq Actual Lim].

• Bit 27 [Bus Reg Tq Lim] indicates the bus voltage regulator is active and limiting the regenerative torque.

• Bit 28 [-0 Torq Ena] indicates that the torque reference is limited to zero because Par 157 [Logic Ctrl State] bit 9 [Torq Ref En] is off.

• Bit 29 [-0 Curr Ena] indicates that the current reference is limited to zero because Par 157 [Logic Ctrl State] bit 11 [CurrRef En] is off.

305

Mtr TorqCurr Ref

Displays the torque current reference present at the output of the current rate limiter.
100% is equal to 1 per unit (pu) rated motor torque.

Units:
Default:
Min/Max:

P.U.
0.0000
-/+8.0000

Real

306

DC Bus Voltage

Displays measured bus voltage.

Units:
Default:
Min/Max:

Volt
0.0000
0.0000/1000.0000

Real

307

Output Voltage

Displays RMS line-to-line fundamental motor voltage. This data is averaged and updated
every 50 milliseconds.

Units:
Default:
Min/Max:

Volt
0.00
0.00/3000.00

Real

308

Output Current

Displays measured RMS motor current.

Units:
Default:
Min/Max:

Amps
0.00
0.00/10000.00

Real

309

% Motor Flux

Displays the motor flux in % of nominal.

Units:
Default:
Min/Max:
Comm Scale:

%
100.0
0.0/100.0
100 = 4096

16-bit
Integer

310

Output Freq

Displays the motor stator frequency.

Units:
Default:
Min/Max:

Hz
0.00
-/+250.00

Real

311

Output Power

Motor Power is the calculated product of the torque reference and motor speed feedback.
A 125mS filter is applied to this result. Positive values indicate motoring power; negative
values indicate regenerative power.

Units:
Default:
Min/Max:

Hp
0.00
-/+9999.00

Real

312

MotorFluxCurr FB

Displays the measured per unit motor flux producing current.

Units:
Default:
Min/Max::

P.U.
0.0000
0.0000/1.0000

Real

No.

Name
Description

Values

Li

nkab

le

Read

-Wr

it

e

Da

ta

T

ype

Options

Reser

ved

Reser

ved

-0

Cu

rr

Ena

-0

T

orq

En

a

Bus Reg Lim

-T

or

q Cur

Li

m

Regen

Pwr

Lim

-T

or

q Lim

-Sp

dReg Open

-Dr

iv

eProtCL

-Dr

iv

ePr

ot

OL

-C

ur

re

nt

Li

m

-I

q Cal

c

0

Iq

fr

om -

-MCS Ws Lim

-MCS Iq

Li

m

Reser

ved

Reser

ved

+0

Cu

rr

En

a

+0

T

orq

En

a

Atu

ne Tq Lim

+T

or

q Cur

Lim

Mtr

ng Pwr

Lim

+T

or

q Limit

+SpdRe

g Op

en

+Dr

iv

eProtC

L

+Dr

iv

eProtOL

+Cur

re

nt Lim

+Iq

Ca

lc

0

Iq

fr

om +

+MCS W

s

Li

m

+MCS Iq Lim

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = False
1 = True

Advertising