Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 38

Advertising
background image

1-24

Installation/Wiring

Table 1.L TB1 - Row B (Bottom) Terminals

Terminal

Signal

Description

Related

Pa

ra

m

et

er

B11

Analog Input #1 (-)

+/-10.0V DC or +/-1.0V DC bipolar,
differential input.

(1)

13 bit + sign,

20k ohm input impedance

800, 802,
803, 804,
805

B10

Analog Input #1 (+)

B9

Analog Input Shield

Optional connection point for
analog input shield.

(2)

B8

Analog Input #2 (-)

+/-10.0V DC or +/-1.0V DC bipolar,
differential input.

(1)

13 bit + sign,

20k ohm input impedance

806, 808,
809, 810,
811

B7

Analog Input #2 (+)

B6

Analog Output #1 (+)

+/-10.0V DCDC bipolar, differential
output, 11 bit + sign, 2k ohm
minimum load

812, 814,
815, 817,
818

B5

Analog Output #1 Return (-)

B4

Analog Output Shield

Optional connection point for
analog output shield.

(2)

B3

Analog Output #2 (+)

+/-10.0V DC bipolar, differential
output, 11 bit + sign, 2k ohm
minimum load

813, 819,
820, 822,
823,

B2

Analog Output #2 Return (-)

B1

Analog Output Shield

Optional connection point for
analog shields.

(1)

Refer to

Analog Input Settings on page 1-32

for necessary dip switch settings.

(2)

Analog shields should connect to common at the signal source, if possible. Shields for signals from ungrounded devices, such as analog
tachometers, should connect to an analog shield terminal point at the drive.

11

10

9

8

7

6

5

4

3

B1

2

Advertising