Installation/Wiring

1-11

Table 1.D Power Terminal Block Specifications

No. Name

Frame

Description

Wire Size Range

(1)

Torque

Terminal Bolt Size

(2)

Maximum

Minimum

Maximum

Recommended

Power Terminal Block 1

Input power and motor
connections

4.0 mm

2

(10 AWG)

0.5 mm

2

(22 AWG)

1.7 N-m
(15 lb.-in.)

0.8 N-m
(7 lb.-in.)

2

Input power and motor
connections

10.0 mm

2

(6 AWG)

0.8 mm

2

(18 AWG)

1.7 N-m
(15 lb.-in.)

1.4 N-m
(12 lb.-in.)

3

Input power and motor
connections

25.0 mm

2

(3 AWG)

2.5 mm

2

(14 AWG)

3.6 N-m
(32 lb.-in.)

1.8 N-m
(16 lb.-in.)

BR1, BR2

10.0 mm

2

(6 AWG)

0.8 mm

2

(18 AWG)

1.7 N-m
(15 lb.-in.)

1.4 N-m
(12 lb.-in.)

4

Input power and motor
connections

35.0 mm

2

(1/0 AWG)

10 mm

2

(8 AWG)

4.0 N-m
(24 lb.-in.)

4.0 N-m
(24 lb.-in.)

5
(75 HP)

(3)

R, S, T, BR1, BR2, DC+,
DC-, U, V and W

50.0 mm

2

(1/0 AWG)

2.5 mm

2

(14 AWG)

See Note

(4)

See Note

(3)

PE

50.0 mm

2

(1/0 AWG)

4.0 mm

2

(12 AWG)

5
(100 HP)

(3)

R, S, T, DC+, DC-, U, V and
W

70.0 mm

2

(2/0 AWG)

16.0 mm

2

(6 AWG)

BR1, BR2

50.0 mm

2

(1/0 AWG)

2.5 mm

2

(14 AWG)

PE

50.0 mm

2

(1/0 AWG)

4.0 mm

2

(12 AWG)

6

Input power and motor
connections

120.0 mm

2

(4/0 AWG)

2.5 mm

2

(14 AWG)

6 N-m
(52 lb.-in.)

6 N-m
(52 lb.-in.)

SHLD Terminal

1-6

Terminating point for wiring
shields

1.6 N-m
(14 lb.-in.)

1.6 N-m
(14 lb.-in.)

M12

AUX Terminal Block

1-4

Auxiliary Control Voltage

(5)

PS+, PS-

1.5 mm

2

(16 AWG)

0.2 mm

2

(24 AWG)

5-6

4.0 mm

2

(10 AWG)

0.5 mm

2

(22 AWG)

0.6 N-m
(5.3 lb.-in.)

0.6 N-m
(5.3 lb.-in.)

Fan Terminal Block
(Common Bus Only)

5-6

User Supplied Fan Voltage
0V AC, 120V AC, 240V AC

4.0 mm

2

(10 AWG)

0.5 mm

2

(22 AWG)

0.6 N-m
(5.3 lb.-in.)

0.6 N-m
(5.3 lb.-in.)

M10

(1)

Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

(2)

Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.

(3)

Not all terminals present on all drives.

(4)

Refer to the terminal block label inside the drive.

(5)

Auxiliary power:
UL Installation - 300V DC,

±10%, Non UL Installation - 270-600V DC, ±10%.

Frame 1-6, 100 W