Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 77

Advertising
background image

Programming and Parameters

3-23

125

Torque Pos Limit

Sets the external torque limit for positive torque reference values. The external positive
motor torque will not be allowed to exceed this value.

Units:
Default:
Min/Max:

P.U.
2.0000
0.0000/8.0000

✓ ✓ Real

126

Torque Neg Limit

Sets the external torque limit for negative torque reference values. The external negative
motor torque will not be allowed to exceed this value.

Units:
Default:
Min/Max:

P.U.
-2.0000
-8.0000/0.0000

✓ ✓ Real

127

Mtring Power Lim

Sets the maximum motoring (positive) power of the drive. This can be calculated by
multiplying the desired maximum motor torque and the maximum motor speed. A value of
1.0 = nominal motor power.

Units:
Default:
Min/Max:

P.U.
8.0000
0.0000/8.0000

✓ ✓ Real

128

Regen Power Lim

Sets the maximum regenerative (negative) power of the drive. This can be calculated by
multiplying the desired maximum motor torque and the maximum motor speed. A value of
1.0 = nominal motor power.

Units:
Default:
Min/Max:

P.U.
-1.0000
-8.0000/0.0000

✓ ✓ Real

129

Atune Torq Ref

Sets the motor torque that is applied to the motor during the flux current and inertia tests.

Units:
Default:
Min/Max:
Comm Scale:

P.U.
0.5000
0.2500/1.0000
1.0 = P.U. Motor to Torque

✓ ✓ Real

130

Torq Ref TP Sel

Enter or write a value to select torque reference data displayed in Par 131 [Torq Ref TP
Data].

Default:
Options:

0
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

“Zero”
“Zero”

16 “Neg Lim Src”

“Scale Output”

17 “MPwr Par Lim”

“Spd Torque”

18 “RPwr Par Lim”

“TrqModeOut”

19 “+Torq ParLim”

“Actv rqMode”

20 “-Torq ParLim”

“Actv Mod Out”

21 “Nom Bus Volt”

“Torq En In”

22 “Bus Volt Hys”

“NotchFiltOut”

23 “Bus Reg Ref”

“NotchFilt In”

24 “Bus Reg Err”

“Torq Lim In”

25 “Bus Reg Intg”

“Bus Reg Out”

26 “BusReg Clamp”

“Pos Pwr Lim”

27 “BusRegOutput”

“Neg Pwr Lim”

28 “IAA Filt Out”

“PosAtun Torq”

29 “IAA dVf/dt”

“NegAtun Torq”

30 “MC Torq Lim”

“Pos Lim Src”

31 “Int Torq Lim”

131

Torq Ref TP Data

Displays the data selected by Par 130 [Torq Ref TP Sel].

Units:
Default:
Min/Max:
Comm Scale:

P.U.
0.0000
-/+8.0000
1.0 = P.U. Motor to Torque

Real

132

Inert Adapt Sel

Configures the Inertia Adaptation Algorithm (IAA Function). Contains the following
selections:

Default:
Min/Max:

00000000
00000000/00000011

✓ Real

133

Inert Adapt BW

This parameter sets the bandwidth of the Inertia Adaptation function when the IAA
function is selected (Par 132 [Inert Adpt Sel], bit 0 [Inrtia Adapt]). Typical IAA bandwidths
range from 70 to 150 rad/sec with 100 rad/sec nominal best.

If the Load Estimate (Par 132 [Inert Adpt Sel], bit 1 [load Est]) function is selected, then
this parameter sets the natural frequency of a filter in rad/sec. Typical values range from
10 to 150 rad/sec with higher values being more responsive to disturbances but with
increased system noise. There is no nominal best value, but 40 rad/sec is a suggested
starting point. This adjustment may not function well in 'sloppy' geared systems.

If both Inertia Adaptation and Load Estimate functions are active, use a bandwidth setting
of 100 rad/sec.

Units:
Default:
Min/Max:

R/S
100.0000
10.0000/250.0000

✓ Real

134

Inert Adapt Gain

This parameter sets a multiplier of system inertia when the Inertia Adaptation function is
selected (Par 132 [Inert Adpt Sel], bit 0 [Inrtia Adapt]). Higher values may cause high
frequency ringing, while smaller values may cause fundamental load instability. A typical
value is 0.5 This parameter has no affect on the Load Estimate function.

Default:
Min/Max:

0.500
0.300/1.000

✓ Real

No.

Name
Description

Values

Li

nkab

le

Read

-Wr

it

e

Da

ta

T

ype

Bit

Name

Current Function

0

Inrtia Adapt

When set to 1 (on), the IAA function will effect enhanced
stability, higher bandwidths and dynamic stiffness. Useful when
systems with a gear-box becomes disconnected from the load.
Also used with motors that have very little inertia that otherwise
lack dynamic stiffness, even at high bandwidths.

1

Load Est

When set to 1 (on), the Load Estimate option removes or greatly
reduces load disturbances and gives quicker system response.

0 & 1

This mode enhances stability as well as removing load
disturbances.