Programming and Parameters

3-21

90

Spd Reg BW

Sets the bandwidth of the speed regulator in rad/sec. Bandwidth is also referred to as the
crossover frequency. Small signal time response is approximately 1/BW and is the time to
reach 63% of set point. A change to this parameter will cause an automatic update of Pars 81
[Spd Reg P Gain] and 82 [Spd Reg I Gain]. To disable the automatic gain calculation, set this
parameter to a value of zero.

Adjustments to Par 474 [Freq Reg We BW] and Par 475 [Freq Reg Wr BW] may be
necessary when using sensorless feedback.

Units:
Default:
Min/Max:

R/S
10.0000
0.0000/500.0000

Min/Max limited by AutoTune
calculations.

✓ ✓ Real

91

Spd Reg Damping

Sets the damping factor of the drive's characteristic equation and factors in the calculation of
the integral gain. A damping factor of 1.0 is considered critical damp. Lowering the damping
will produce faster load disturbance rejection, but may cause a more oscillatory response.
When Par 90 [Spd Reg BW] is set to zero, damping factor has no effect.

Default:
Min/Max:

1.0000
0.5000/3.0000

✓ ✓ Real

92

SpdReg P Gain Mx

Places a limit on the maximum value of proportional gain in Par 81 [Spd Reg P Gain]. When
gains are automatically calculated, this parameter is necessary to limit the amplification of
noise with increased inertia.

Default:
Min/Max:

100.0000
0.0000/600.0000

✓ ✓ Real

93

SRegFB Filt Gain

Sets the lead term for the speed feedback filter. A value greater than 1 will result in a lead
function and a value less than 1 will result in a lag function. A value of 1 will disable the filter.

Default:
Min/Max:

1.0000
-5.0000/20.0000

✓ ✓ Real

94

SReg FB Filt BW

Sets the frequency for the Speed feedback filter.

Units:
Default:
Min/Max:

R/S
35.0000
0.0000/3760.0000

✓ ✓ Real

95

SRegOut FiltGain

Sets the lead term for the Speed Regulator output filter. A value greater than 1 will result in a
lead function and a value less than 1 will result in a lag function. A value of 1 will disable the
filter.

Default:
Min/Max:

0.7000
-/+5.0000

✓ ✓ Real

96

SReg Out Filt BW

Sets the frequency for the Speed Regulator output filter.

Units:
Default:
Min/Max:

R/S
30.0000
0.0000/3760.0000

✓ ✓ Real

97

Act Spd Reg BW

Displays the actual speed regulator bandwidth or crossover frequency. The value represents
the bandwidth in Par 90 [Spd Reg BW] after the maximum bandwidth limits have been
applied.

Units:
Default:
Min/Max:

R/S
10.0000
0.0000/500.0000

Real

98

Spd Gain TP Sel

Enter or write a value to select the speed gain data displayed in Par 99 [Spd Gain TP Data].

Default:
Options:

0
0
1
2
3
4
5
6
7
8
9
10
11

“Zero”
“Zero”

12 “I Rate Limit”

“Iq Rate BW”

13 “I RtLim Stat”

“Reserved”

14 “PGain Max”

“PGain Max BW” 15 “GnMx LimStat”
“BW Limit”

16 “Damping”

“InertiaMaxBW” 17 “Dmp Lim Stat”
“BW Lim Stat”

18 “Reserved”

“BW Select”

19 “Srls KpMxBW”

“Totl Inertia”

20 “Srls BWLimit”

“TI Lim Stat”

21 “SrlsInrtMxBW”

“Mtr Inertia”

22 “SrlsBWSelect”

“M InrtLStat”

23 “Srls BW Calc”
24 “Snsr BW Calc”

99

Spd Gain TP Data

Displays the value selected by Par 98 [Spd Gain TP Sel].

Default:
Min/Max:

0.0000
0.0000/500.0000

Real

100

Speed Error

The error (difference) between the motor speed reference (+) and the filtered motor speed
feedback (-).

Units:
Default:
Min/Max:
Comm Scale:

RPM
0.0000
-/+14112.0000
Par 4 [Motor NP RPM] = 1.0

Real

101

SpdReg Integ Out

The output value of the Speed Regulator Integral channel.

Units:
Default:
Min/Max:
Comm Scale:

P.U.
0.0000
-/+8.0000
1.0 PU Torque

Real

102

Spd Reg Pos Lim

Sets the positive limit of the Speed regulator output value. The output of the Speed regulator
is limited by adjustable high and low limits.

Units:
Default:
Min.Max:
Comm Scale:

P.U.
3.0000
0.0000/6.0000
Par 4 [Motor NP RPM] = 1.0

✓ ✓ Real

103

Spd Reg Neg Lim

Sets the negative limit of the Speed regulator output value. The output of the Speed
regulator is limited by adjustable high and low limits.

Units:
Default:
Min/Max:
Comm Scale:

P.U.
-3.0000
-6.0000/0.0000
Par 4 [Motor NP RPM] = 1.0

✓ ✓ Real

104

SrLss Spd Reg Kp

Sets the proportional gain of the speed regulator when sensorless motor speed feedback is
used. Value is automatically calculated based on the bandwidth set in Par 106 [Srlss Spd
Reg BW]. Proportional gain may be manually adjusted by setting Par 106 to zero. This gain
setting has no units (per unit torque) / (per unit speed error).

Default:
Min/Max:

8.0000
0.0000/200.0000

✓ Real

No.

Name
Description

Values

Li

nkab

le

Read

-Wr

it

e

Da

ta

T

ype

Advertising