Troubleshooting

4-5

5

Opt Port 0 Loss

A fault on port 0 of the Hi-Resolution Encoder Feedback Option
Card, MDI Option Card, or Resolver Feedback Option Card has
occurred.

Parameter 260 [Hi-Res0 Status] displays the fault status for port 0 of
the Hi-Resolution Encoder Feedback Option Card.

Parameter 267 [Resolver0 Status] displays the fault status for port 0
of the Resolver Feedback Option Card.

6

Opt Port 1 Loss

The Linear sensor portion of the MDI feedback option card has
detected a fault condition.

Parameter 286 [Linear1 Status] displays the fault status for linear
portion of the MDI feedback Option Card.

9

Slink Comm Fail

A SynchLink communication fault has occurred.

Parameter 1229 [SL Error Status] displays SynchLink errors.

10

Drive Power Loss

DC Bus voltage has fallen below the minimum value

• Parameter 306 [DC Bus Voltage] displays bus voltage

• Parameter 330 [Fault TP Data] displays the minimum value when

parameter 329 [Fault TP Sel] is set to five

The drive must first complete precharge before this check is made

11

Motor Oload Trip

A motor overload trip has occurred.

Parameter 308 [Output Current] is squared, scaled and integrated
over time. When this integrated value exceeds 1.0, this Exception
Event occurs.

The integrator's output can be viewed in Parameter 330 [Fault TP
Data] when parameter 329 [Fault TP Sel] is set to 13 “Mtr OL Outpt”.
The overload integration rate is affected by parameters 336 [Service
Factor], 337 [Mtr I2T Curr Min], 338 [Mtr I2T Spd Min] and 339 [Mtr
I2T Calibrat].

Reduce mechanical load

12

Motor Oload Pend

A motor overload is pending.

Parameter 308 [Output Current] is squared, scaled and integrated
over time. When this integrated value exceeds 0.5, this Exception
Event occurs.

The integrator's output can be viewed in Parameter 330 [Fault TP
Data] when parameter 329 [Fault TP Sel] is set to 13 “Mtr OL Outpt”.
The overload integration rate is affected by parameters 336 [Service
Factor], 337 [Mtr I2T Curr Min], 338 [Mtr I2T Spd Min] and 339 [Mtr
I2T Calibrat].

Reduce mechanical load

13

Motor Stalled

The motor has stalled. These three conditions have occurred at the
same time for the amount of time specified in parameter 373 [Motor
Stall Time]:

• Drive is not stopped (parameter 150 [Logic State Mach] not equal

to zero)

• Drive is on limit (parameter 304 [Limit Status] not equal to zero)

• Drive is at zero speed (parameter 155 [Logic Status], bit 13 [At

Zero Spd] is set).

1. Increase torque limit
2. Reduce mechanical load

14

Inv Otemp Pend

Parameter 313 [Heatsink Temp] is within 10

° C of maximum.

View the maximum heat sink temperature in parameter 348 [Drive
OL TP Data] when parameter 347 [Drive OL TP Se] is set to 30
[fMaxHsDegc].

15

Inv Otemp Trip

Parameter 313 [Heatsink Temp] is above the maximum limit or
temperature sensor has failed (shorted or open.

See parameter 346 [Drive OL Status], bit 0 [NTC Shorted] and bit 1
[NTC Open].

No.

Name

Description

Action