3-52

Programming and Parameters

390

SL MultErr Cnfg

Enter a value to configure the Drive Module's response to SynchLink Multiplier error.
Refer to Par 1034 [SL Mult State] for possible causes for multiplier errors.

• 0 “Ignore” - Configures the drive to continue running, as normal, when this event

occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the

appropriate fault bit, in response this event

• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the

appropriate fault bit, in response this event

Default:
Options:

2
0
1
2
3
4

“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”

391

DPI CommLoss Cfg

Enter a value to configure the drive's response to the failure of a DPI port.

• 0 “Ignore” - Configures the drive to continue running, as normal, when this event

occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the

appropriate fault bit, in response this event

• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the

appropriate fault bit, in response this event

Default:
Options:

2
0
1
2
3
4

“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”

392

NetLoss DPI Cnfg

Enter a value to configure the drive's response to communication fault from a network
card at a DPI port.

• 0 “Ignore” - Configures the drive to continue running, as normal, when this event

occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the

appropriate fault bit, in response this event

• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the

appropriate fault bit, in response this event

Default:
Options:

2
0
1
2
3
4

“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”

393

BusUndervoltCnfg

Enter a value to configure the drive's response to DC Bus voltage falling below the
minimum value.

• 0 “Ignore” - Configures the drive to continue running, as normal, when this event

occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

Default:
Options:

1
0
1
2

“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”

No.

Name
Description

Values

Li

nkab

le

Read

-Wr

it

e

Da

ta

T

ype

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 390 [SL MultErr Cnfg] lets you determine the action
of the drive if communications are disrupted. By default this parameter causes the drive to fault and coast to a stop. You can
set this parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this parameter
does not create hazards of injury or equipment damage.

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 391 [DPI CommLoss Cfg] lets you determine the
action of the drive if communications are disrupted. By default this parameter causes the drive to fault and coast to a stop.
You can set this parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this
parameter does not create hazards of injury or equipment damage.

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 392 [NetLoss DPI Cnfg] lets you determine the
action of the drive if communications are disrupted. By default this parameter causes the drive to fault and coast to a stop.
You can set this parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this
parameter does not create hazards of injury or equipment damage.