Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 71

Advertising
background image

Programming and Parameters

3-17

20

Speed Ref DPI

Sets the speed reference that the drive should use when selected in Par 16 [Speed Ref Sel].
A device communicating on a DPI port (typically a HIM) provides this value.

Units:
Default:
Min/Max:
Comm Scale:

RPM
0.00000
-/+14112.00000
Par 4 [Motor NP RPM] = 1.0

Real

21

Speed Trim 1

Provides an additive trim value to Par 46 [Scaled Spd Ref].

Units:
Default:
Min/Max:
Comm Scale:

RPM
0.0000
-/+14112.0000
Par 4 [Motor NP RPM] = 1.0

✓ ✓ Real

22

Speed Trim 2

Provides an additive speed trim value to Par 47 [Spd Trim1 SpdRef] with a Lead/Lag filter.
The Position regulator output is linked to this parameter by default. This speed trim value
affects the speed reference input to the speed regulator.

Units:
Default:
Min/Max:
Comm Scale:

RPM
0.0000
-/+14112.0000
Par 4 [Motor NP RPM] = 1.0

✓ ✓ Real

23

Speed Trim 3

Provides a scalable speed trim value that will be added to Par 47 [Spd Trim1 SpdRef]. Par 24
[SpdTrim 3 Scale] scales this value prior to the trim value affecting the speed reference.

Units:
Default:
Min/Max:
Comm Scale:

RPM
0.0000
-/+14112.0000
Par 4 [Motor NP RPM] = 1.0

✓ ✓ Real

24

SpdTrim 3 Scale

Par 23 [Speed Trim 3] is multiplied by this number. This number can be used to scale the
value of Par 23 [Speed Trim 3].

Default:
Min/Max:

1.0000
-/+1000.0000

✓ ✓ Real

25

STrim2 Filt Gain

Sets the lead term for the Par 22 [Speed Trim 2] filter. A value greater than 1 will result in a
lead function and a value less than 1 will result in a lag function. A value of 1 will disable the
filter.

Default:
Min/Max:

1.0000
-/+15.0000

✓ ✓ Real

26

SpdTrim2 Filt BW

Sets the frequency for the Speed Trim 2 filter.

Units:
Default:
Min/Max:

R/S
200.0000
0.0000/1000.0000

✓ ✓ Real

30

Rev Speed Limit

Sets a limit on the speed reference in the negative direction. This value can be entered as a
negative value or zero.

Units:
Default:
Min/Max:
Comm Scale:

RPM
-2205.0000
-14112.0000/0.0000
Par 4 [Motor NP RPM] = 1.0

✓ Real

31

Fwd Speed Limit

Sets a limit on the speed reference in the positive direction. This value can be entered as a
positive value or zero.

Units:
Default:
Min/Max:
Comm Scale:

RPM
2205.0000
0.0000/14112.0000
Par 4 [Motor NP RPM] = 1.0

✓ Real

32

Accel Time

Sets the rate of acceleration for all speed increases, with time in seconds to base speed.
Accel Rate = Par 4 [Motor NP RPM] / Par 32 [Accel Time]

Units:
Default:
Min/Max:

Sec
10.0000
0.0100/6553.5000

✓ ✓ Real

33

Decel Time

Sets the rate of deceleration for all speed decreases, with time in seconds to base speed.
Decel Rate = Par 4 [Motor NP RPM] / Par 33 [Decel Time]

Units:
Default:
Min/Max:

Sec
10.0000
0.0100/6553.5000

✓ ✓ Real

34

S Curve Time

Sets the S time (Round In and Round Out ) in seconds. Half of the time specified is added to
the beginning and half to the end of the applied ramp. The S time is independent of speed
and results in a trapezoidal torque profile. For example:

Units:
Default:
Min/Max:

Sec
0.5000
0.0000/4.0000

✓ ✓ Real

35

SpdRef Filt Gain

Sets the lead term for the Speed Reference filter. A value greater than 1 will result in a lead
function and a value less than 1 will result in a lag function. A value of 1 will disable the filter.

Default:
Min/Max:

1.0000
-/+5.0000

✓ ✓ Real

36

SpdRef Filt BW

Sets the frequency for the Speed Reference filter.

Units:
Default:
Min/Max:

R/S
0.0000
0.0000/500.0000

✓ ✓ Real

37

Spd Ref Bypass

The speed command after the limit, ramp and s-curve blocks. Link a source directly to this
parameter to bypass these blocks.

Units:
Default:
Min/Max:
Comm Scale:

RPM
0.0000
-/+14112.0000
Par 4 [Motor NP RPM] = 1.0

✓ ✓ Real

38

Speed Ref Scale

This parameter is multiplied with the value in Par 44 [Filtered Spd Ref] to produce the value in
Par 46 [Scaled Spd Ref].

Default:
Min/Max:

1.0000
-/+1000.0000
x 1

✓ ✓ Real

No.

Name
Description

Values

Li

nkab

le

Read

-Wr

it

e

Da

ta

T

ype

S Curve Time = 1.0 second

Speed

Time in Seconds

0.5 sec.

Accel Time = 5.0 seconds

Total Ramp Time = 6.0 seconds

0.5 sec.

Advertising