Supplemental Information

A-11

480 Volt AC Input Frames 1…6 Drive Protection Devices

20DC650

11 355

-

655

850 (1 per phs)
425 (2 per phs)

1400

850 (1 per phs)
425 (2 per phs)

1900

170M5813

1900

1000

-

315

594

750 (1 per phs)
375 (2 per phs)

1300

750 (1 per phs)
375 (2 per phs)

1700

170M5813

1700

800

20DC730

11 400

-

735

1000 (1 per phs)
500 (2 per phs)

1600

1000 (1 per phs)
500 (2 per phs)

2100

170M5813

2100

1200

-

355

655

850 (1 per phs)
425 (2 per phs)

1400

850 (1 per phs)
425 (2 per phs)

1900

170M5813

1900

1000

(1)

Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.

(2)

Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(3)

Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(4)

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

(5)

Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.

Drive Catalog

Number

Fr

am

e

kW Rating

Input

Ratings

Dual Element Time Delay Fuse

Non-Time Delay Fuse

Bussmann Style Semi-

Conductor Fuse

Circuit

Breaker

(3)

Motor Circuit

Protector

(5)

ND

HD

Amps

Min.

(1)

Max.

(2)

Min.

(1)

Max.

(3)

Max.

(4)

Max.

(5)

Drive

Catalog

Number

Fr

am

e

HP Rating Input Ratings Dual Element

Time Delay Fuse

Non-Time Delay

Fuse

Circuit

Breaker

(3)

Motor

Circuit

Protector

(5)

140M Motor Starter with Adjustable Current Range

(6)(7)

ND

HD

Amps

kVA

Min.

(1)

Max.

(2)

Min.

(3)

Max.

(4

)

Max.

(4)

Max.

(6)

Available Catalog Numbers

(8)

Minimum Enclosure
Volume (in.

3

)

(9)

20DD2P1

1

1

0.7
5

1.6

1.4

3

6

3

8

15

3

M-C2E-B25

7269

20DD3P4

1

2

1.5

2.6

2.2

4

8

4

12

15

7

M-C2E-B40

M-D8E-B40

7269

20DD5P0

1

3

2

3.9

3.2

6

10

6

20

20

7

M-C2E-B63

M-D8E-B63

7269

20DD8P0

1

5

3

6.9

5.7

10

15

10

30

30

15

M-C2E-C10

M-D8E-C10

M-F8E-C10

7269

20DD011

1

7.5

5

9.5

7.9

15

20

15

40

40

15

M-C2E-C16

M-D8E-C16

M-F8E-C16

7269

20DD014

1

10

7.5

12.5

10.4

17.5

30

17.5

50

50

20

M-C2E-C16

M-D8E-C16

M-F8E-C16

7269

20DD022

1

15

10

19.9

16.6

25

50

25

80

80

30

M-D8E-C25

M-F8E-C25

7269

20DD027

2

20

15

24.8

20.6

35

60

35

100

100

50

M-F8E-C32

7269

20DD034

2

25

20

31.2

25.9

40

70

40

125

125

50

M-F8E-C45

7269

20DD040

3

30

25

36.7

30.5

50

90

50

150

150

50

M-F8E-C45

13630

20DD052

3

40

30

47.7

39.7

60

110

60

200

200

70

20DD065

3

50

40

59.6

49.6

80

125

80

250

250

100

20DD077

4

60

72.3

60.1

100

170

100

300

300

100

50

59.6

49.6

80

125

80

250

250

100

20DD096

5

75

90.1

74.9

125

200

125

350

350

125

60

72.3

60.1

100

170

100

300

300

100

20DD125

5

100

117

97.6

150

250

150

500

375

150

75

90.1

74.9

125

200

125

350

350

125

20DD156

6

125

146.5

121.7

200

350

200

600

450

250

100

131

97.6

175

250

175

500

375

250

20DD180

6

150

169

140.5

225

400

225

600

500

250

125

147

121.7

200

350

200

600

450

250

20DD248

6

200

232.8

188

300

550

300

700

700

400

150

169

140.5

225

400

225

600

500

250

(1)

Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.

(2)

Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(3)

Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(4)

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

(5)

Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.

(6)

Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.

(7)

Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.

(8)

The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See

Bulletin 140M Motor Protection Circuit Breakers Application Ratings

.

(9)

When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger
enclosure.

Advertising