A-15

540 Volt DC Input Frames 9…11 Drive Protection Devices

650 Volt DC Input Frames 1…6 Drive Protection Devices

Drive Catalog Number

Frame kW Rating

DC Input Ratings

Fuse

Bussmann Style Fuse

ND

HD

Amps

20DH261

9

132

-

307

500

170M6608

-

110

241

500

170M6608

20DH300

9

160

-

353

630

170M6610

-

132

288

630

170M6610

20DH385

10

200

-

453

700

170M6611

-

160

353

700

170M6611

20DH460

10

250

-

541

900

170M6613

-

200

453

900

170M6613

20DH500

10

250

-

589

500 (2 per phs)

170M6608

-

250

494

500 (2 per phs)

170M6608

20DH590

11

315

-

695

550 (2 per phs)

170M6609

-

250

612

550 (2 per phs)

170M6609

20DH650

11

355

-

765

630 (2 per phs)

170M6610

-

315

695

630 (2 per phs)

170M6610

20DH730

11

400

-

859

700 (2 per phs)

170M6611

-

355

765

700 (2 per phs)

170M6611

Drive Catalog Number

Frame

HP Rating

DC Input Ratings

Fuse

Non-Time Delay Fuse

(2)

(2)

The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC). Battery supplies or
MG sets are not included. The following devices were validated to break current of the derived power DC Bus: Disconnects: Allen-Bradley Bulletin No.
1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. Fuses: Bussmann Type JKS, all sizes;Type 170M, Case Sizes 1,
2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please contact the factory.

ND

HD

Amps

20DD2P1

1

1

0.75

1.9

6

JKS-6

20DD3P4

1

2

1.5

3.0

6

JKS-6

20DD5P0

1

3

2

4.5

10

JKS-10

20DD8P0

1

5

3

8.1

15

HSJ15

20DD011

1

7.5

5

11.1

20

HSJ20

20DD014

1

10

7.5

14.6

30

HSJ30

20DD022

1

15

10

23.3

40

HSJ40

20DD027

2

20

15

28.9

50

HSJ50

20DD034

2

25

20

36.4

60

HSJ60

20DD040

3

30

25

42.9

80

HSJ80

20DD052

3

40

30

55.7

90

HSJ90

20DD065

3

50

40

69.6

100

HSJ100

20DD077

4

60

50

84.5

150

HSJ150

20DJ096

(1)

(1)

Also applies to “R” voltage class. Fuses must be applied in the (+) leg and (-) leg of the DC Common Bus.

5

75

105.3

175

HSJ175

60

84.5

175

HSJ175

20DJ125

(1)

5

100

137.1

200

HSJ200

75

105.3

200

HSJ200

20DJ156

(1)

6

125

171

300

HSJ300

100

137.1

300

HSJ300

20DJ180

(1)

6

150

198

400

HSJ400

125

171.2

400

HSJ400

20DJ248

(1)

6

200

272

400

HSJ400

150

198

400

HSJ400

Advertising