1-28

Installation/Wiring

Input/Output

Connection Examples — 3-Wire Control

Required Parameter Changes

High Speed Inputs
12 or 24V DC

Sourcing High Speed Inputs, Used for 3 Wire Control - using
the internal power supply

• Set the value of Parameter 839 [DigIn2 Sel] to a

value of 1 - Normal Stop

• Set the value of Parameter 840 [DigIn3 Sel] to a

value of 2 - Start

• Set Parameter 153 [Control Options] / bit 8

“3WireControl”

Note: +12V and +24V are also available from

TB1 Top 10 & 11.

Sourcing High Speed Inputs, Used for 3 Wire Control - using an
external power supply

Table 1.O TB2 - Row T (Top) Wiring Examples

3 4 5 6

2

1

Start

Stop

7

POWER

COMMON

(RETURN)

EXTERNAL

POWER SUPPLY

3 4 5 6

Start

Stop

7