1-30

Installation/Wiring

Table 1.P TB2 - Row B (Bottom) Terminals

Terminal

Signal

Description

Related

Pa

ra

m

et

er

B13

Encoder Signal A

Secondary encoder interface.
5 or 12V DC switch
selectable

(1)

, Nominal

current draw per channel @
12V DC 45 mA, @5V DC 32
mA
Maximum input frequency for
Encoders 0 & 1 is 500 kHz.

(1)

Refer to

Encoder Input Settings on page 1-32

for necessary dip switch settings.

222, 240,
241, 242,
243, 244,
245, 246,
247, 248

B12

Encoder Signal Not A

B11

Encoder Signal B

B10

Encoder Signal Not B

B9

Encoder Signal Z

B8

Encoder Signal Not Z

B7

Shield

Connection point for encoder
shield.

B6

Unused

B5

Relay Output

Relay contact output.
Rating: 5A @ 24V DC
Resistive, 2A 24V DC
Inductive

824, 841,
842

B4

Relay Output Return

B3

Unused

B2

Power Supply +12V DC (B) (+)

15/2V DC power supply for
secondary encoder interface.
Rating 300 mA

(2)

(3)

(2)

This power supply supports only the secondary encoder interface. Do not use it to power circuits outside of the
drive

(3)

To enable 5V supply, set Jumper J6 (located in the Main Control Board) to positions T2 and T3. Default 12V
supply is set to T1 and T2.

B1

Power Supply +12V DC Return (B) (-)

B1 2

3

4

5

6

7

8

9 10 11 12 13