3-50

Programming and Parameters

382

MC Cmd Lim Cnfg

Enter a value to configure the drive's response to a Motor-Controller (MC) Command
Limitation exception event. This event is triggered when the motor-controller detects limit
of the command values used in the motor-controller, and returns the exception event to
the Velocity Position Loop (VPL).

• 0 “Ignore” Configures the drive to continue running, as normal, when this event occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

Default:
Options:

2
0
1
2

“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”

383

SL CommLoss Data

Enter a value to determine what is done with the data received from SynchLink when a
communication loss occurs.

• 0 “Zero Data” - Resets data to zero

• 1 “Last State” - Holds data in its last state

Default:
Options:

1
0
1

“Last State”
“Zero Data”
“Last State”

384

SL CommLoss Cnfg

Enter a value to configure the drive's response to SynchLink communication loss. Refer
to Par 1229 [SL Error Status] for possible causes of communication loss.

• 0 “Ignore” - Configures the drive to continue running, as normal, when this event

occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the

appropriate fault bit, in response this event

• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the

appropriate fault bit, in response this event

Default:
Options:

2
0
1
2
3
4

“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”

385

Lgx CommLossData

Enter a value to configure what drive does with the data received from the DriveLogix
controller when the connection is closed or times out.

• 0 “Zero Data” - Resets data to zero

• 1 “Last State” - Holds data in its last state

Default:
Options:

1
0
1

“Last State”
“Zero Data”
“Last State”

386

Lgx OutOfRunCnfg

Enter a value to configure the drive's response to the DriveLogix processor being in
Non-Run mode. Non-Run modes include Program, Remote-Program and Faulted.

• 0 “Ignore” - Configures the drive to continue running, as normal, when this event

occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the

appropriate fault bit, in response this event

• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the

appropriate fault bit, in response this event

Default:
Options:

2
0
1
2
3
4

“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”

No.

Name
Description

Values

Li

nkab

le

Read

-Wr

it

e

Da

ta

T

ype

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 383 [SL CommLoss Data] lets you determine the
action of the drive if communications are disrupted. By default this parameter causes the drive to hold the data in its last
state. You can set this parameter so that the drive resets the data to zero. Precautions should be taken to ensure that the
setting of this parameter does not create hazards of injury or equipment damage.

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 384 [SL CommLoss Cnfg] lets you determine the
action of the drive if communications are disrupted. By default this parameter causes the drive to fault and coast to a stop.
You can set this parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this
parameter does not create hazards of injury or equipment damage.

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 385 [Lgx CommLossData] lets you determine the
action of the drive if communications are disrupted. By default this parameter causes the drive to hold the data in its last
state. You can set this parameter so that the drive resets the data to zero. Precautions should be taken to ensure that the
setting of this parameter does not create hazards of injury or equipment damage.

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 386 [Lgx OutOfRunCnfg] lets you determine the
action of the drive if communications are disrupted. By default this parameter causes the drive to fault and coast to a stop.
You can set this parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this
parameter does not create hazards of injury or equipment damage.