105

SrLss Spd Reg Ki

Sets the integral gain of the speed regulator when sensorless motor speed feedback is
used. This value is automatically calculated based on the bandwidth set in Par 106 [Srlss
Spd Reg BW]. Integral gain may be manually adjusted by setting Par 106 to zero. Units
are '/Sec' (per unit torque/sec) / (per unit speed error).

Units:
Default:
Min/Max:

/Sec
8.0000
0.0000/4095.8000

106

SrLss Spd Reg BW

Sets the bandwidth of the speed regulator when sensorless motor speed feedback is
used. Units are in rad/sec. Bandwidth is also referred to as the crossover frequency.
Small integral time response is approximately 1/BW and is the time to reach 63% of set
point. A change to this parameter will cause an automatic update of Parameters 104
[SrLss Spd Reg Kp] and 105 [SrLss Spd Reg Ki]. To disable the automatic gain
calculation, set this parameter to zero. The maximum limit for this parameter is
determined by Par 354 [Iq Rate Limit], the ratio of Par 8 [Motor Inertia] to Par 9 [Total
Inertia], and Par 107 [SrLss Kp Max].

Units:
Default:
Min/Max:

R/S
10.0000
0.0000/30.0000

107

SrLss Kp Max

Places a limit on the maximum value of proportional gain in Par 104 [SrLss Spd Reg Kp],
for use when sensorless motor speed feedback is used. When gains are autmatically
calculated, this parameter is necessary to limit the amplification of noise with increased
inertia.

Default:
Min/Max:

20.0000
20.0000/35.0000

108

Spd Reg TP Sel

Enter or write a value to select speed regulator data displayed in Par 109 [Spd Reg TP
Data].

Default:
Options:

0
0
1
2
3
4
5
6
7
8
9
10

“Zero”
“Zero”

11 “SrLss ZeroWe”

“Spd FiltOut”

12 “I GainParLim”

“Servo Lock”

13 “P GainParLim”

“Spd+ServLock” 14 “SrvLck ParLm”
“Prop Output”

15 “AntiBkup PLm”

“Intg Input

16 “Droop ParLim”

“Scld Int Pre”

17 “Pos Lim Stat”

“Sel Int Pre”

18 “Neg Lim Stat”

“Droop Output”

19 “Limiter Out”

“Out Lim Stat”

20 “Active Pgain”

“Intg Hold”

21 “Active Igain”

109

Spd Reg TP Data

Displays the data selected by Par 108 [Spd Reg TP Sel].

Units:
Default:
Min/Max:

P.U.
0.0000
-/+8.0000

Real

110

Spd/Torq ModeSel

Selects the source for the drive torque reference.

Default:
Options:

1
0
1
2
3

“Speed Reg”
“Zero Torque”

4

“Max Spd/Torq”

“Speed Reg”

5

“Sum Spd/Torq”

“Torque Ref”

6

“AbsMn Spd/Tq”

“Min Spd/Torq”

111

Torque Ref 1

Supplies an external motor torque reference to the drive. This parameter is divided by the
value in Par 112 [Torq Ref1 Div]. A value of 1.0 represents rated torque of the motor.

Default:
Min/Max:
Comm Scale:

0.0000
-/+2200000000.0000
1.0 Rated Motor Torque

✓ ✓ Real

112

Torq Ref1 Div

Par 111 [Torque Ref 1] is divided by this number. Use this parameter to scale the value of
Par 111 [Torque Ref 1].

Default:
Min/Max:

1.0000
-/+2200000000.0000

✓ Real

113

Torque Ref 2

Supplies an external motor torque reference to the drive. This parameter is multiplied by
the value in Par 114 [Torq Ref2 Mult]. A value of 1.0 represents rated torque of the motor.

Default:
Min/Max:
Comm Scale:

0.0000
-/+2200000000.0000
1.0 Rated Motor Torque

✓ ✓ Real

114

Torq Ref2 Mult

Par 113 [Torque Ref 2] is multiplied by this number. Use this parameter to scale the value
of Par 113 [Torque Ref 2].

Default:
Min/Max:

1.0000
-/+2200000000.0000

✓ ✓ Real

115

Torque Trim

The amount added to the Torque Ref 1 & 2 before the Speed/Torque Mode Selector. A
value of 1.0 represents rated torque of the motor.

Units:
Default:
Min/Max:
Comm Scale:

P.U.
0.0000
-/+8.0000
1.0 Rated Motor Torque

✓ ✓ Real

116

Torque Step

The amount added to the selected Torque Reference before notch filtering or limits are
applied. A value of 1.0 represents rated torque of the motor.

Units:
Default:
Min/Max:
Comm Scale:

P.U.
0.0000
-/+8.0000
1.0 Rated Motor Torque

✓ ✓ Real

117

Notch Filt Mode

Notch enabled.

Default:
Options:

0
0
1

“No Filter”
“No Filter”

2

“IIR Notch”

“Reserved”

118

Notch Filt Freq

The center frequency for Notch filter.

Units:
Default:
Min/Max:

Hz
135.0000
0.0000/500.0000

✓ ✓ Real

123

Torq PosLim Actl

Sets the internal torque limit for positive torque reference values. The positive internal
motor torque will not be allowed to exceed this value.

Units:
Default:
Min/Max:

P.U.
1.0000
0.0000/8.0000

Real

124

Torq NegLim Actl

Sets the internal torque limit for negative torque reference values. The internal negative
motor torque will not be allowed to exceed this value.

Units:
Default:
Min/Max:

P.U.
-1.0000
-8.0000/0.0000

Real