Programming and Parameters

3-29

186

PI Prop Gain

Controls the proportional gain of the Process Control regulator. If the proportional gain is
1.0, the regulator output equals 1 pu for 1 pu error.

Default:
Min/Max:

8.0000
0.0000/200.0000

✓ ✓ Real

187

PI Integ Time

Controls the integral gain of the Process Control regulator. If the integrator time is 1.0, the
regulator output equals 1 pu in 1 second for 1 pu error.

Units:
Default:
Min/Max:

/Sec
8.0000
0.0000/4000.0000

✓ ✓ Real

188

PI Integ HLim

The high limit of the integral gain channel for the Process Control regulator. A value of 1
can represent either base motor speed, motor rated torque, or 100% for some external
function.

Units:
Default:
Min/Max:

P.U.
0.1000
0.0000/8.0000

✓ ✓ Real

189

PI Integ LLim

The low limit of the integral gain channel for the Process Control regulator. A value of 1
can represent either base motor speed, motor rated torque, or 100% for some external
function.

Units:
Default:
Min/Max:

P.U.
-0.1000
-8.0000/0.0000

✓ ✓ Real

190

PI Integ Output

Displays the output value of the integral channel of the Process Control regulator. A value
of 1 can represent either base motor speed, motor rated torque, or 100% for some
external function.

Units:
Default:
Min/Max:

P.U.
0.0000
-/+8.0000

Real

191

PI High Limit

The high limit of the Process Control regulator output. A value of 1 can represent either
base motor speed, motor rated torque, or 100% for some external function.

Units:
Default:
Min/Max:

P.U.
0.1000
0.0000/8.0000

✓ ✓ Real

192

PI Lower Limit

The low limit of the Process Control regulator output. A value of 1 can represent either
base motor speed, motor rated torque, or 100% for some external function.

Units:
Default:
Min/Max:

P.U.
-0.1000
-8.0000/0.0000

✓ ✓ Real

193

PI TP Sel

Enter or write a value to select Process Control PI data displayed by Par 194 [PI TP
Data].

Default:
Options:

0
0
1
2
3
4
5

“Zero”
“Zero”

6

“On Out Limit”

“PI Error”

7

“Extern Hold”

“LPF Output”

8

“Hold Status”

“P Gain Term”

9

“Enbl Status”

“Reg Output”

10 “Time Axis En”

“On Intg Lim”

194

PI TP Data

Displays the data selected by Par 193 [PI TP Sel].

Units:
Default:
Min/Max:

P.U.
0.0000
-/+8.0000

Real

200

Time Axis Rate

Sets rate (1/sec) for the Time Function Generator to ramp from and output of 0 to 1 and
from 1 to 0.

Units:
Default:
Min/Max:

/Sec
1.0000
0.0100/20.0000

✓ ✓ Real

201

Time Axis Output

The output of the Time Function Generator. When the Time Function Generator is
enabled by Par 183 [PI Command] bit 1 [Enable] or Par 151 [Logic Command] bit 3 [Time
Axis En], the value of this parameter ramps from 0 to 1 at a rate determined by Par 200
[Time Axis Rate]. Conversely, when the Function Generator is disabled, the value of this
parameter ramps from 1 to 0.

Default:
Min/Max:

0.0000
0.0000/1.0000

Real

204

LimGen Y axis Mx

Sets Par 207 [Limit Gen Hi Out] and Par 208 [Limit Gen Lo Out] when the absolute value
of Par 206 [LimGen X axis In] is greater than or equal to 1.

Units:
Default:
Min/Max:

P.U.
0.2500
0.0000/8.0000

✓ ✓ Real

205

LimGen Y axis Mn

Sets Par 207 [Limit Gen Hi Out] and Par 208 [Limit Gen Lo Out] when the absolute value
of Par 206 [LimGen X axis In] is equal to 0.

Units:
Default:
Min/Max:

P.U.
0.0500
0.0000/8.0000

✓ ✓ Real

206

LimGen X axis In

The X axis input to the Limit Generator. Typically this parameter is linked to a speed
reference or to Par 201 [Time Axis Output].

Default:
Min/Max:

0.0000
-/+8.0000

✓ ✓ Real

207

Limit Gen Hi Out

Displays the positive output of the Limit Generator. When Par 206 [Limit Gen X axis In] is
greater than or equal to 1, this value equals Par 204 [LimGen Y axis Mx]. When Par 206
[LimGen X axis In] is equal to 0, this value equals Par 205 [LimGen Y axis Mn]. For
values of X Axis input between 0 and 1, the value of this parameter is interpolated from Y
axis min and max values. Typically this parameter is linked to Par 191 [PI High Limit].

Units:
Default:
Min/Max:

P.U.
8.0000
0.0000/8.0000

Real

208

Limit Gen Lo Out

Displays the negative output of the Limit Generator. The value of this parameter is the
negative of Par 207 [Limit Gen Hi Out]. Typically it is linked to Par 192 [PI Lower Limit].

Units:
Default:
Min/Max:

P.U.
-8.0000
-8.0000/0.0000

Real