Installation/Wiring

1-27

Table 1.O TB2 - Row T (Top) Wiring Examples

Input/Output

Connection Examples

Required Parameter Changes

Primary Encoder Interface -
Supports 12V DC differential
encoders with internal power
supply.

5V DC differential encoders
may require external power
supply and special jumper
settings. Refer to

Main Control

Board I/O Configuration
Settings on page 1-32

for

external power supply and
jumper settings.

For 5V DC differential encoders
with internal power supply, set
Jumper J6 to positions T2 and
T3.

Primary Encoder - using internal power supply

• Set the value of Parameter 222 [Motor Fdbk

Sel] to a value of 0 - Encoder 0, so the drive will
use this encoder as the primary motor speed
feedback device.

• Set the value of Parameter 232 [Encoder0 PPR]

to match the encoder’s resolution.

Primary Encoder - using external power supply

13

12

11

10

9

8

7

2

1

Power

Common
(Return)

A

A

B

B

Z

Z

Case Ground

13

12

11

10

9

8

7

Power

Common
(Return)

A

A

B

B

Z

Z

Case Ground

Shield

Power

Common

(Return)