Table 1.O TB2 - Row T (Top) Wiring Examples
Input/Output
Connection Examples
Required Parameter Changes
Primary Encoder Interface -
Supports 12V DC differential
encoders with internal power
supply.
5V DC differential encoders
may require external power
supply and special jumper
settings. Refer to
Board I/O Configuration
Settings on page 1-32
for
external power supply and
jumper settings.
For 5V DC differential encoders
with internal power supply, set
Jumper J6 to positions T2 and
T3.
Primary Encoder - using internal power supply
• Set the value of Parameter 222 [Motor Fdbk
Sel] to a value of 0 - Encoder 0, so the drive will
use this encoder as the primary motor speed
feedback device.
• Set the value of Parameter 232 [Encoder0 PPR]
to match the encoder’s resolution.
Primary Encoder - using external power supply
13
12
11
10
9
8
7
2
1
Power
Common
(Return)
A
A
B
B
Z
Z
Case Ground
13
12
11
10
9
8
7
Power
Common
(Return)
A
A
B
B
Z
Z
Case Ground
Shield
Power
Common
(Return)