Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 93

Advertising
background image

Programming and Parameters

3-39

267

Reslvr0 Status

Indicates the status of the resolver option card port 0.

• Bit 0 [-Cable Tune] indicates that the cable tuning test is active.

• Bit 1 [-Tune Result] indicates the tuning parameter type. When set, it indicates the tuning is using the parameter database. When cleared, it indicates the

tuning is using derived data.

• Bit 2 [-Mtr Turning] indicates that the motor is turning.

• Bit 4 [Energized] indicates the resolver is energized.

• Bit 8 [Open Wire] indicates a problem with the cable (open circuit).

• Bit 9 [Power Supply] indicates a problem with the option card's power supply.

• Bit 10 [Diag Fail] indicates the option card has failed its power-up diagnostics.

268

Reslvr0 TP Sel

Enter or write a value to select Fault data displayed in Par 269 [Reslvr0 TP Data].

Default:
Options:

0
0
1
2
3

“Zero”
“Zero”

4

“R0 EPR”

“R0 Edge Time” 5

“R0 Edge Mode”

“R0 dEdge”

6

“R0 dTheta”

“R0 dTime”

7

“R0 Delta2Err”

269

Reslvr0 TP Data

Displays the data selected by Par 268 [Reslvr0 TP Sel].

Default:
Min/Max:

0
-/+2147483648

32-bit
Integer

270

Reslvr0 SpdRatio

Specifies the speed ratio for the resolver option card port 0. The speed ratio comes from
the following formula. Speed ratio = electrical revolutions / mechanical revolutions = pole
count / 2.

Default:
Options:

1
1
2
3

2 poles (x1)
2 Poles (x1)

4

8 Poles (x4)

4 Poles (x2)

5

10 Poles(x5)

6 Poles (x3)

271

Reslvr0 Carrier

Specifies the resolver carrier frequency for the resolver option card port 0.

Units:
Default:
Min/Max:

Hz
0
0/10000

32-bit
Integer

272

Reslvr0 In Volts

Specifies the resolver input voltage for the resolver option card port 0.

Units:
Default:
Min/Max:

Volt
0.0000
0.0000/31.0810

Floating
Point

273

Rslvr0 XfrmRatio

Specifies the resolver transform ratio for the resolver option card port 0.

Default:
Min/Max:

0.0000
0.0000/4.0950

Floating
Point

274

Reslvr0 CableBal

Specifies the resolver cable balance for the resolver option card port 0.

Default:
Min/Max:

0.0000
0.0000/255.0000

Floating
Point

275

Reslvr0 Type Sel

Specifies the type of resolver used.

Default:
Options:

0
0
1
2
3
4
5
6
7

“Disabled”
“Disabled”

8

“Reserved”

“T2014/2087x1” 9

“1326Ax 460v”

“T2014/2087x2” 10 “Reserved”
“T2014/2087x5” 11 “Reserved”
“MPL 460v”

12 “Reserved”

“Reserved”

13 “Reserved”

“Siemens 1FT6” 14 “AmciR11XC107”
“PrkrHn ZX600”

276

FB Opt1 Posit

Displays the position feedback (accumulator) from port 1 of the feedback option card.

Default:
Min/Max:

0
-/+2147483648

32-bit
Integer

277

FB Opt1 Spd Fdbk

Displays the speed feedback from port 1 of the feedback option card.

Units:
Default:
Min/Max:
Comm Scale:

RPM
0.0000
-/+14000.0000
Par 4 [Motor NP RPM] = 1.0

Floating
Point

279

Opt 1 Regis Ltch

Displays registration data from port 1 of the feedback option card. This data is the value
of the position reference counter, latched by the external strobes. The strobe signal used
to trigger the latch is configurable by Par 280 [Opt 1 Regis Cnfg].

Default:
Min/Max:

0
-/+2147483648

32-bit
Integer

No.

Name
Description

Values

Li

nkab

le

Read

-Wr

it

e

Da

ta

T

ype

Options

Res

er

ve

d

Res

er

ve

d

Res

er

ve

d

Res

er

ve

d

Selec

t OK

Diag F

ail

P

ow

er Supp

ly

Ope

n Wire

Res

er

ve

d

Res

er

ve

d

Res

er

ve

d

E

ner

gi

ze

d

-Ca

ble

Co

mp

-Mt

r T

ur

nin

g

-T

une

Re

sult

-Ca

ble

T

une

Default

0

0

0

0

1

1

1

1

1

1

1

1

1

1

1

1

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = False
1 = True

Advertising