Programming and Parameters

3-49

375

Inv OT Pend Cnfg

Enter a value to configure the drive's response to a Inverter Over-Temperature (OT)
Pending exception event. This event is triggered when the Inverter NTC (Temperature
protection) function detects the heat-sink temperature reaches to the overload warning
level.

• 0 “Ignore” - Configures the drive to continue running, as normal, when this event

occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the

appropriate fault bit, in response this event

• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the

appropriate fault bit, in response this event

Default:
Options:

1
0
1
2
3
4

“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”

376

Inv OL Pend Cnfg

Enter a value to configure the drive's response to an Inverter Overload (OL) Pending
exception event. This event is triggered when one of the Inverter Protection
Current-Over-Time functions (Open Loop or Closed Loop) detects current and
temperature at warning levels.

• 0 “Ignore” - Configures the drive to continue running, as normal, when this event

occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the

appropriate fault bit, in response this event

• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the

appropriate fault bit, in response this event

Default:
Options:

1
0
1
2
3
4

“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”

377

Inv OL Trip Cnfg

Enter a value to configure the drive's response to an Inverter Overload (OL) Trip
exception event. This event is triggered when one of the Inverter Protection
Current-Over-Time functions (Open Loop or Closed Loop) detects current and
temperature at a fault level.

• 0 “Ignore” Configures the drive to continue running, as normal, when this event occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

Default:
Options:

1
0
1
2

“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”

378

Interp Flt Cnfg

Enter a value to configure the drive's response when a Synchronization input to the
Interpolator has been lost or has become excessively irregular.

• 0 “Ignore” - Configures the drive to continue running, as normal, when this event

occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the

appropriate fault bit, in response this event

• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the

appropriate fault bit, in response this event

Default:
Options:

2
0
1
2
3
4

“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”

379

Ext Flt/Alm Cnfg

Enter a value to configure the drive's response to an External Input exception event. The
event is triggered by a digital input that is configured for auxiliary fault or auxiliary aux
fault by choosing option 11 “Aux Fault” or 12 “AuxFault Inv” in Pars 838 [DigIn 1 Sel], 839
[DigIn 2 Sel], or 840 [DigIn 3 Sel].

• 0 “Ignore” - Configures the drive to continue running, as normal, when this event

occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the

appropriate fault bit, in response this event

• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the

appropriate fault bit, in response this event

Default:
Options:

2
0
1
2
3
4

“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”

381

PreChrg Err Cnfg

Enter a value to configure the drive's response to a Precharge Error exception event.

• 0 “Ignore” Configures the drive to continue running, as normal, when this event occurs

• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit

when this event occurs

• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate

fault bit, in response this event

Default:
Options:

2
0
1
2

“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”

No.

Name
Description

Values

Li

nkab

le

Read

-Wr

it

e

Da

ta

T

ype