Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 111

Advertising
background image

Programming and Parameters

3-57

474

Freq Reg We BW

Sets the electrical (stator) frequency bandwidth for the Frequency Regulator, which
estimates motor speed when sensorless feedback is selected.

Must always be set to a value higher than Par 475 [Freq Reg Wr BW].

Default:
Min/Max:

150
0/32767

✓ 16-bit

Integer

475

Freq Reg Wr BW

Sets the rotor (speed) frequency bandwidth for the Frequency Regulator, which estimates
motor speed when sensorless feedback is selected.

Must always be set to a value higher than Par 97 [Act Spd Reg BW]. Normal applications
should use a value approximately 50% greater than Par 97. Applications with large
dynamic ranges can use values 200-300% greater than Par 97. However large values
can result in pull-outs and unstable operation.

Default:
Min/Max:

30
0/32767

✓ 16-bit

Integer

476

Slip Gain Comp

Provides slip gain compensation for sensorless speed adjustment.

Units:
Default:
Min/Max:

%
100.00
0.00/400.00

✓ 16-bit

Integer

477

Est Theta Delay

Active only in Permanent Magnet motor mode (when Par 485 [Motor Ctrl Mode] equals 2
“PMag Motor”). Provides a delay for the function that compares the estimated rotor
position and the data from the position sensor.

Units:
Default:
Min/Max:

mSec
10
2/1024

✓ 16-bit

Integer

485

Motor Ctrl Mode

Enter a value to select the operating mode for the Motor Control (MC).

• 0 “FOC” - (Field Oriented Control) is induction motor control with voltage adaptation.

• 1 “FOC 2” (Field Oriented Control 2) is induction motor control with temperature

adaptation.

• 2 “Pmag Motor” - (Permanent Magnet Motor Control) is permanent magnet motor

operation.

• 4 (Test) - Is the test mode.

Default:
Options:

0
0
1
2

“FOC”
“FOC”

3

“Reserved”

“FOC 2”

4

“Test”

“PMag Motor”

486

Rated Slip Freq

Displays the control slip frequency, determined from Par 3 [Motor NP Hertz] and Par 4
[Motor NP RPM]. Measured by the autotune procedure. Do not change this value.

Units:
Default:
Min/Max:
Comm Scale:

Hz
0.470
0.000/32.000
x 1000

✓ 16-bit

Integer

487

Motor NTC Coef

Defines a coefficient used to calculate the rotor temperature from the measured stator
temperature. Used only in Field Oriented Control - 2 (FOC2) mode.

Units:
Default:
Min/Max:

%
100
50/200

✓ 16-bit

Integer

488

Flux Current

Specifies the magnetizing current that produces rated flux in the motor in a per unit
(percent representation). Measured by the autotune procedure. Do not change this value.

Units:
Default:
Min/Max:
Comm Scale:

%
30.00
0.00/75.00
x 100

✓ 16-bit

Integer

490

StatorInductance

Displays the sum of the stator and cable inductances of the motor in per unit (percent
representation), as determined by the autotune procedure. Scaled to percent of rated
motor impedance. Do not change this value.

Units:
Default:
Min/Max:
Comm Scale:

%
100.00
0.00/799.99
100 = 8192\

✓ 16-bit

Integer

491

StatorResistance

Displays the sum of the stator and cable resistances of the motor in per unit (percent
representation), as determined by the autotune procedure. Scaled to percent of rated
motor impedance. Do not change this value.

Units:
Default:
Min/Max:
Comm Scale:

%
1.00
0.00/100.00
100 = 8192

✓ 16-bit

Integer

492

Leak Inductance

Displays the sum of the motor stator, rotor leakage, and motor cable inductances in per
unit (percent representation), as determined by the autotune procedure. Scaled to
percent of rated motor impedance. Do not change this value.

Units:
Default:
Min/Max:
Comm Scale:

%
20.00
0.00/100.00
100 = 8192

✓ 16-bit

Integer

493

Leak Indc Sat 1

Displays the leakage inductance correction for the first overload level as determined by
the autotune procedure.

Units:
Default:
Min/Max:

%
100.00
25.00/100.00

16-bit
Integer

494

Leak Indc Sat 2

Displays the leakage inductance correction for the first overload level as determined by
the autotune procedure.

Units:
Default:
Min/Max:

%
100.00
25.00/100.00

16-bit
Integer

500

Bus Util Limit

Sets the maximum allowed bus voltage utilization for the Motor Control. Do not change
this value. Higher values may result in control instability or over-current faults.

Units:
Default:
Min/Max:
Comm Scale:

%
90.0
0.0/100.0
100 = 8192

✓ 16-bit

Integer

501

Torque En Dly

Sets the delay between the time the drive is enabled and the time the Motor Control
applies torque.

Units:
Default:
Min/Max:
Comm Scale:

mSec
100
0/32767
100 = 8192

✓ 16-bit

Integer

502

Rotor Resistance

Displays rotor resistance, as determined by the autotune procedure. Scaled to percent of
rated motor impedance. Do not change this value.

Units:
Default:
Min/Max:
Comm Scale:

%
1.00
0.00/100.00
100 = 8192

✓ 16-bit

Integer

No.

Name
Description

Values

Li

nkab

le

Read

-Wr

it

e

Da

ta

T

ype

Advertising