Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 178

Advertising
background image

A-14

Supplemental Information

690 Volt AC Input Frames 5 and 6 Drive Protection Devices

540 Volt DC Input Frames 1…6 Drive Protection Devices

Drive

Catalog

Number

Fr

am

e

kW Rating

Input Ratings

Dual Element Time Delay

Fuse

Non-Time Delay Fuse

Circuit Breaker

(3)

Motor Circuit Protector

(5)

ND

HD

Amps

kVA

Min.

(1)

Max.

(2)

Min.

(2)

Max.

(3)

Max.

(4)

Max.

(5)

20DF052

5

45

–

46.9

59.5

60

110

60

175

175

–

–

37.5

40.1

48.0

50

90

50

150

150

–

20DF060

5

55

–

57.7

68.9

80

125

80

225

225

–

–

45

46.9

59.5

60

110

60

175

175

–

20DF082

5

75

–

79.0

94.4

100

200

100

375

375

–

–

55

57.7

68.9

80

125

80

225

225

–

20DF098

5

90

–

94.7

113

125

200

125

375

375

–

–

75

79.0

94.4

100

200

100

375

375

–

20DF119

6

110

–

115

138

150

250

150

400

–

–

–

90

92.9

113

125

200

125

375

–

–

20DF142

6

132

–

139

165.9

175

300

175

450

–

–

–

110

115

137

150

250

150

400

–

–

(1)

Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.

(2)

Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(3)

Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(4)

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

(5)

Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.

Drive Catalog Number

Frame

kW Rating

DC Input Ratings

Fuse

Non-Time Delay Fuse

(2)

(2)

The power source to Common Bus inverters must be derived from AC voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC). Battery supplies or
MG sets are not included. The following devices were validated to break current of the derived power DC Bus: Disconnects: Allen-Bradley Bulletin No.
1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. Fuses: Bussmann Type JKS, all sizes;Type 170M, Case Sizes
1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please contact the factory.

ND

HD

Amps

20DC3P5

1

1.5

1.1

3.7

8

JKS-8

20DC5P0

1

2.2

1.5

5.3

10

JKS-10

20DC8P7

1

4

3.0

9.3

15

HSJ15

20DC011

1

5.5

4

12.6

20

HSJ20

20DC015

1

7.5

5.5

16.8

25

HSJ25

20DC022

1

11

7.5

24

40

HSJ40

20DC030

2

15

11

33.2

50

HSJ50

20DC037

2

18.5

15

40.9

70

HSJ70

20DC043

3

22

18.5

47.5

90

HSJ90

20DC056

3

30

22

61.9

100

HSJ100

20DC072

3

37

30

80.5

125

HSJ125

20DC085

4

45

37

95.1

150

HSJ150

20DH105

(1)

(1)

Also applies to “P” voltage class. Fuses must be applied in the (+) leg and (-) leg of the DC Common Bus.

5

55

–

120.2

175

HSJ175

–

45

95.1

175

HSJ175

20DH125

(1)

5

55

–

120.2

200

HSJ200

–

45

95.1

200

HSJ200

20DH140

5

75

–

159

250

HSJ250

–

55

120.2

250

HSJ250

20DH170

(1)

6

90

–

192

350

HSJ350

–

75

159

350

HSJ350

20DH205

(1)

6

110

–

226

350

HSJ350

–

90

192

350

HSJ350

20DH260

(1)

6

132

–

298

400

HSJ400

–

110

226

400

HSJ400