Supplemental Information

690 Volt AC Input Frames 5 and 6 Drive Protection Devices

540 Volt DC Input Frames 1…6 Drive Protection Devices

Drive

Catalog

Number

Fr

am

e

kW Rating

Input Ratings

Dual Element Time Delay

Fuse

Non-Time Delay Fuse

Circuit Breaker

(3)

Motor Circuit Protector

(5)

ND

HD

Amps

kVA

Min.

(1)

Max.

(2)

Min.

(2)

Max.

(3)

Max.

(4)

Max.

(5)

20DF052

5

45

46.9

59.5

60

110

60

175

175

37.5

40.1

48.0

50

90

50

150

150

20DF060

5

55

57.7

68.9

80

125

80

225

225

45

46.9

59.5

60

110

60

175

175

20DF082

5

75

79.0

94.4

100

200

100

375

375

55

57.7

68.9

80

125

80

225

225

20DF098

5

90

94.7

113

125

200

125

375

375

75

79.0

94.4

100

200

100

375

375

20DF119

6

110

115

138

150

250

150

400

90

92.9

113

125

200

125

375

20DF142

6

132

139

165.9

175

300

175

450

110

115

137

150

250

150

400

(1)

Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.

(2)

Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(3)

Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(4)

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

(5)

Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.

Drive Catalog Number

Frame

kW Rating

DC Input Ratings

Fuse

Non-Time Delay Fuse

(2)

(2)

The power source to Common Bus inverters must be derived from AC voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC). Battery supplies or
MG sets are not included. The following devices were validated to break current of the derived power DC Bus: Disconnects: Allen-Bradley Bulletin No.
1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. Fuses: Bussmann Type JKS, all sizes;Type 170M, Case Sizes
1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please contact the factory.

ND

HD

Amps

20DC3P5

1

1.5

1.1

3.7

8

JKS-8

20DC5P0

1

2.2

1.5

5.3

10

JKS-10

20DC8P7

1

4

3.0

9.3

15

HSJ15

20DC011

1

5.5

4

12.6

20

HSJ20

20DC015

1

7.5

5.5

16.8

25

HSJ25

20DC022

1

11

7.5

24

40

HSJ40

20DC030

2

15

11

33.2

50

HSJ50

20DC037

2

18.5

15

40.9

70

HSJ70

20DC043

3

22

18.5

47.5

90

HSJ90

20DC056

3

30

22

61.9

100

HSJ100

20DC072

3

37

30

80.5

125

HSJ125

20DC085

4

45

37

95.1

150

HSJ150

20DH105

(1)

(1)

Also applies to “P” voltage class. Fuses must be applied in the (+) leg and (-) leg of the DC Common Bus.

5

55

120.2

175

HSJ175

45

95.1

175

HSJ175

20DH125

(1)

5

55

120.2

200

HSJ200

45

95.1

200

HSJ200

20DH140

5

75

159

250

HSJ250

55

120.2

250

HSJ250

20DH170

(1)

6

90

192

350

HSJ350

75

159

350

HSJ350

20DH205

(1)

6

110

226

350

HSJ350

90

192

350

HSJ350

20DH260

(1)

6

132

298

400

HSJ400

110

226

400

HSJ400