Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 127

Advertising
background image

Programming and Parameters

3-73

768

PositReg P Gain

Sets position regulator gain as measured from position error to speed reference. The gain
number is identically equal to position regulator bandwidth in rad/sec. For example: A
gain of 10 means that a per unit position error of 0.1 sec. will effect a 1.0 pu speed
change (1 per unit position error is the distance traveled in 1 sec. at base motor speed).
The maximum value of this parameter is typically 1/3 of the speed bandwidth (rad/sec)
but may be set considerably higher with careful tuning of the speed regulator output lead/
lag filter.

Units:
Default:
Min/Max:

R/S
4.0000
0.0000/200.0000

v

✓ Real

769

Position Error

Actual position error in motor pulse counts. When the position regulator is not enabled,
this 32 bit integer register is initialized to zero. When the position regulator is enabled, this
parameter contains the running value of position error, often referred to as “following
error”.

Default:
Min/Max:

0
-/+2147483648

32-bit
Integer

770

PositReg Integ

Sets position regulator integral gain as measured from position error to velocity reference.
It has gain units of (per unit velocity/sec) / (per unit position) and is unit compatible with
Par 768 [PositReg P Gain]. An integral gain of 25 means that a per unit position error of
0.1 sec will effect a 2.5 pu speed change per sec. A typical maximum value is _*[PositReg
P Gain]2. Note: 1 per unit position is the distance traveled in 1 sec. at base motor speed.

Units:
Default:
Min/Max:
Comm Scale:

/S2
4.0000
0.0000/1000.0000
x 1

✓ ✓ Real

771

PositReg Droop

Position Droop limits the low frequency gain of the position regulators integral channel to
a value of (1/droop). It provides a means to fine tune the stability for load mounted
feedback devices where lost motion may cause a problem. Typically, position droop will
have a value that is less than (1/position gain), perhaps even zero for tightly coupled
loads. Position droop has a gain value of (per unit position) / (per unit speed). Note: 1 per
unit position is the distance traveled in 1 sec. at base motor speed.

Default:
Min/Max:

0.0000
0.0000/0.2500

✓ ✓ Real

772

XReg Integ LoLim

The negative limit of the position integrator.

Units:
Default:
Min/Max:
Comm Scale:

RPM
-176.4000
-14112.0000/0.0000
Par 4 [Motor NP RPM] = 1.0

✓ ✓ Real

773

XReg Integ HiLim

The positive limit of the position integrator.

Units:
Default:
Min/Max:
Comm Scale:

RPM
176.4000
0.0000/14112.0000
Par 4 [Motor NP RPM] = 1.0

✓ ✓ Real

774

XReg Integ Out

The output of the position regulator integral channel after application of the limits. This
output is set to zero if the integral gain is set to zero or the integrator is not enabled.

Units:
Default:
Min/Max:
Comm Scale:

RPM
0
-/+14112.0000
Par 4 [Motor NP RPM] = 1.0

Real

775

XReg Spd LoLim

The negative limit of total position regulator output. Point to point mode uses this
parameter to set the reverse speed reference.

Units:
Default:
Min/Max:
Comm Scale:

RPM
-176.4000
-14112.0000/0.0000
Par 4 [Motor NP RPM] = 1.0

✓ ✓ Real

776

XReg Spd HiLim

The positive limit of total position regulator output. Point to point mode uses this
parameter to set the forward speed reference.

Units:
Default:
Min/Max:
Comm Scale:

RPM
176.4000
0.0000/14112.0000
Par 4 [Motor NP RPM] = 1.0

✓ ✓ Real

777

Posit TP Select

Enter or write a value to select position regulator data displayed in Par 778 [Posit TP Data
Int] and Par 779 [Posit TP DataReal].

Default:
Options:

0
0
1
2
3
4
5
6
7
8

“Zero”
“Zero”

9

“Limiter Out”

“del Xos Vout”

10 “Ref EGR In”

“del Xcmd”

11 “OffsetSpdLim”

“del Act Load”

12 “PtoP SpdLim”

“del Act Mtr”

13 “Sec per Edge”

“Integ Error”

14 “Edge per Sec”

“Xprop Out”

15 “Ratio Guess”

“Reserved”

16 “Sync Count”

“PreLim Xvout”

778

PositTP Data Int

Displays the data selected by Par 777 [Posit TP Select]. This display should only be used
if the selected value is integer data.

Default:
Min/Max:

0
-/+2147483648

32-bit
Integer

779

PositTP DataReal

Displays the data selected by Par 777 [Posit TP Select] in RPM. This display should only
be used if the selected value is floating point data.

Units:
Default:
Min/Max:
Comm Scale:

RPM
0.0000
-/+3.8880799961088.0000
Par 4 [Motor NP RPM] = 1.0

Real

780

PositDetct1 Stpt

Provides the setpoint for Position Watch 1. Position Watch 1 is enabled and configured
with Par 740 [Position Control] bits 16 & 17. Position Watch 1 compares this value with
Par 784 [Posit Detct1 In] and sets bit 8 [Posit Watch1] of Par 741 [Position Status] when
the appropriate condition is satisfied.

Default:
Min/Max:

0
-/+2147483648

32-bit
Integer

781

PositDetct2 Stpt

Provides the setpoint for Position Watch 2. Position Watch 2 is enabled and configured
with Par 740 [Position Control] bits 18 & 19. Position Watch 2 compares this value with
Par 785 [Posit Detct2 In] and sets bit 9 [Posit Watch2] of Par 741 [Position Status] when
the appropriate condition is satisfied.

Default:
Min/Max:

0
-/+2147483648

✓ ✓ 32-bit

Integer

No.

Name
Description

Values

Li

nkab

le

Read

-Wr

it

e

Da

ta

T

ype

Advertising