Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 99

Advertising
background image

Programming and Parameters

3-45

329

Fault TP Sel

Enter or write a value to select Fault data displayed in Par 330 [Fault TP Data].

Default:
Options:

0
0
1
2
3
4
5
6
7
8
9
10
11

“Zero”
“Zero”

12 “Mtr OL Input”

“Abs OverSpd”

13 “Mtr OL Outpt”

“EE Pwr State”

14 “MtrStallTime”

“Inv DataStat”

15 “MC Handshake”

“Run Time Err”

16 “VPL Handshak”

“LowBus Thres” 17 “MC Diag”
“LowBus Detct”

18 “PwrLossState”

“PwrLosBusVlt” 19 “12 volt loss”
“MCPLosBusVlt” 20 “PwrEE Chksum”
“MC Flt Reset”

21 “Db Read Cnt1”

“VPL FltReset”

22 “Db Read Cnt2”

“VPL TaskErr”

23 “Db Read Cnt3”

330

Fault TP Data

Displays the data selected by Par 329 [Fault TP Sel].

Default:
Min/Max:

0
-/+2200000000

Real

331

Fault Stop Mode

Displays the action taken by the drive during the last fault. When a fault occurs, an action
is taken as a result of that fault.

Default:
Options:

0
0
1
2

“Ignore”
“Ignore”

3

“Flt RampStop“

“Alarm”

4

“FltCurLimStop”

“FltCoastStop”

335

Abs OverSpd Lim

Sets an incremental speed above Par 31 [Fwd Speed Limit] and below Par 30 [Rev
Speed Limit] that is allowable before the drive indicates its speed is out of range.

Units:
Default:
Min/Max:
Comm Scale:

RPM
352.8000
0.0000/1750.0000
Par 4 [Motor NP RPM] = 1.0

✓ Real

336

Service Factor

Sets the minimum level of current that causes a motor overload trip under continuous
operation. Current levels below this value will not result in an overload trip. For example, a
service factor of 1.15 implies continuous operation up to 115% of nameplate motor
current.

Units:
Default:
Min/Max:

P.U.
1.1500
1.0000/2.0000

✓ Real

337

Mtr I2T Curr Min

Sets the minimum current threshold for the motor overload (I

2

T) function. The value

indicates the minimum current at the minimum speed, Par 338 [Mtr I2T Spd Min], and
these are the first current/speed breakpoint. From this point the current threshold is linear
to the value specified by Par 336 [Service Factor].

Units:
Default:
Min Max:

P.U.
0.5000
0.0500/2.0000

✓ Real

338

Mtr I2T Spd Min

Sets the minimum speed for the motor overload (I

2

T) function. The value indicates the

minimum speed below the minimum current threshold, Par 337 [Mtr I2T Curr Min], and
these are the first current/speed breakpoint. From this point the current threshold is linear
to the value specified by the motor service factor Par 336 [Service Factor]. For more
information, please see

Motor Overload on page C-3

.

Units:
Default:
Min/Max:

P.U.
1.0000
0.0500/1.0000

✓ Real

339

Mtr I2T Calibrat

Sets the current calibration level for the motor overload (I

2

T) function. The value indicates

the current level that the drive will fault at this current in 60 seconds.

Units:
Default:
Min/Max:

P.U.
2.0000
1.1000/4.0000

✓ Real

340

Mtr I2T Trp ThrH

Displays the trip threshold current for the motor overload (I

2

T) function. The value

depends on the motor speed, and is calculated from the minimum current, Par 337 [Mtr
I2T Curr Min], the minimum speed, Par 338 [Mtr I2T Spd Min], and the motor service
factor, Par 336 [Service Factor].

Units:
Default:
Min/Max:

P.U.
1.1500
0.0500/2.0000

Real

343

OL OpnLp CurrLim

Displays the current limit set by the Open Loop Inverter Overload (OL) function. This
function sets this current limit based on stator current feedback and the current ratings of
the drive - continuous and short term (three-second rating). Typically the drive will have a
sixty-second rating of 110% of continuous current and a three-second rating at 150% of
the continuous current. Under normal operating conditions, the open loop function sets
this current limit to the short term (three-second) rating. If the function detects an
overload, it lowers the limit to the continuous level. After a period of time (typically one to
three minutes), the function returns the limit to the short term rating.

Units:
Default:
Min/Max:

P.U.
8.0000
0.0000/8.0000

Real

344

OL ClsLp CurrLim

Displays the current limit set by the Closed Loop Inverter Overload (OL) function. This
function will set a current limit level based on the values in Par 358 [Iq Ref Limited], Par
313 [Heatsink Temp] and the thermal characteristics of the drive. Under normal operating
conditions, the function typically sets the limit at 250% of the continuous drive rating. If
the function determines that the power device junction temperature is approaching
maximum, it will reduce this limit to the level required to prevent additional heating of the
inverter. This level could be as low as the continuous rating of the drive. If the inverter
temperature decreases, the function will raise the limit to a higher level. Disable this
protection by setting bit 13 [OL ClsLpDsbl] of Par 153 [Control Options].

Units:
Default:
Min/Max:

P.U.
8.0000
0.0000/8.0000

Real