Terminal (see, Figure 1.3, Figure 1.3 typical power terminal block location – Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 26: 12 installation/wiring, Frame 1 frame 2, Frame 5, Fan terminal block, Frame 3 & 4

Advertising
background image

1-12

Installation/Wiring

Figure 1.3 Typical Power Terminal Block Location

BR1 B

SHLD

SHLD

V/T2 W/T3

PE R/L1 S/L2 T/L3

AUX IN+ AUX OUT–

Optional

Communications

Module

75C Cu Wire

6 AWG [10MM

2

] Max.

12 IN. LBS.
1.4 N-M

} TORQUE

WIRE
STRIP

CONTROL

POWER

BR1

BR2

DC+

DC–

PE

U/T1

V/T2

W/T3

R/L1

S/L2

T/L3

Use 75C Wire Only

#10-#14 AWG

Torque to 7 in-lbs

!

DANGER

Frame 1

Frame 2

WIRE RANGE: 14-1/0 AWG (2.5-35 MM

2

)

TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY

POWER TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (16-35 MM

2

)

TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM

2

)

TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

17

21

INPUT AC

OUTPUT

Optional

Communications

Module

9

120

VAC

240

VAC

0

VAC

Frame 5

Fan Terminal

Block

Optional

Communications

Module

L2

L1

T3

T2

T1

L3

INPUT

OUTPUT

USE 75 C

COPPER WIRE

ONLY

TORQUE
52 IN-LB

(6 N-M)

BR2

PS+

PS–

BR1

DC+

DC–

USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)

22-10
AWG

5.3 IN-LB
(0.6 N-M)

WIRE STRIP

Frame 6

BR1 BR2 DC+ DC- U/T1 V/T2 W/T3 R/L1 S/L2 T/L3

Optional

Communications

Module

PE B

PE A

75C Cu Wire

3 AWG [25MM

2

] Max.

16 IN. LBS.
1.8 N-M

} TORQUE

WIRE
STRIP

CONTROL

POWER

AUX IN

+ –

SHLD

SHLD

PE

75C Cu Wire

6 AWG [10MM2] Max.

BR1 BR2

12 IN. LBS.
1.4 N-M

} TORQUE

Frame 3 & 4