1-32

Installation/Wiring

Main Control Board I/O Configuration Settings

Figure 18 Main Control Board Dip Switches

Analog Input Settings

Switch SW1-1 configures the scaling of Analog Input #1. Switch SW1-2
configures the scaling of Analog Input #2. Open the switch for +/-10.0V DC
operation. Close the switch for +/-1.0V DC operation.

Encoder Input Settings

Dip switch SW2 on the main control board configures the encoder inputs
for 5V DC or 12V DC operation. Switches SW2-2, 4, and 6 are for the
primary encoder. Set these switches to match the encoder output
specifications. Open these switches for 12V DC operation, close them for
5V DC operation.

1 2

FRONT - TOP VIEW

SIDE VIEW

UP = OPEN = OFF

DOWN = CLOSED= ON

SW1

OPEN

1

FRONT - TOP VIEW

SIDE VIEW

UP = OPEN = OFF

DOWN = CLOSED= ON

SW2

2 3 4 5 6 7 8

J6

Pin 3

Pin 2

Pin 1

Analog Input #1
Scaling

+/-10.0V DC +/-1.0V DC

SW1-1

Open

Closed

Analog Input #2
Scaling

+/-10.0V DC +/-1.0V DC

SW1-2

Open

Closed

Primary Encoder

SW2-2

SW2-4

SW2-6

5V DC Operation

Closed

Closed

Closed

12V DC Operation

Open

Open

Open

Secondary Encoder SW2-1

SW2-3

SW2-5

5V DC Operation

Closed

Closed

Closed

12V DC Operation

Open

Open

Open

Encoder Power
Supply Voltage

Jumper
Position

5V DC

2-3

12V DC

1-2