Setpt 1 data, Setpt 2 data, Figure c.5 at setpoint 1 status – Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 216: Figure c.6 above setpoint 2 status

Advertising
background image

C-6

Application Notes

Setpt 1 Data

Provides data for comparison of Par 172 [Setpt 1 Data] to Par 173 [Setpt1
TripPoint], driving bit 16 [At Setpt 1] of Par 155 [Logic Status].

Figure C.5 At Setpoint 1 Status

Setpt 2 Data

Provides data for comparison of Par175 [Setpt 2 Data] to Par 176 [Setpt2
TripPoint], driving bit 17 [Above Setpt 2] of Par 155 [Logic Status].

Figure C.6 Above Setpoint 2 Status

P173 [Setpt1 TripPoint]

P172 [Setpt 1 Data]

bit 16 [At Setpt 1] tur

ns on

bit 16 [At Setpt 1] tur

ns off

bit 16 [At Setpt 1] tur

ns on

bit 16 [At Setpt 1] tur

ns off

bit 16 [At Setpt 1] tur

ns on

bit 16 [At Setpt 1] tur

ns on

bit 16 [At Setpt 1] tur

ns off

bit 16 [At Setpt 1] tur

ns on

bit 16 [At Setpt 1] tur

ns off

bit 16 [At Setpt 1] tur

ns off

P173 [Setpt1 TripPoint] + P174 [Setpt 1 Limit]

P173 [Setpt1 TripPoint] + 2 x P174 [Setpt 1 Limit]

P173 [Setpt1 TripPoint] - P174 [Setpt 1 Limit]

P173 [Setpt1 TripPoint] - 2 x P174 [Setpt 1 Limit]

Time

P176 [Setpt 2 TripPoint] - P177 [Setpt 2 Limit]

P175 [Setpt 2 Data]

bit 17 [Abo

ve Setpt 2] tur

ns on

bit 17 [Abo

ve Setpt 2] tur

ns off

0

Time

P176 [Setpt 2 TripPoint]

P176 [Setpt 2 TripPoint] - 2 x P177 [Setpt 2 Limit]