Led indications, Led indications -2 – Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 156

Advertising
background image

4-2

Troubleshooting

LED Indications

Figure 4.1 Drive Status Indicators

Table 4.A Drive Status Indicators

DRIVE

DRIVE

SYNCHLINK

ENABLE

3

2

1

4

Frame 1 Shown

#

Name

Color

State

Description

Action

DR

IV

E

Po

w

er

S

tr

uc

tu

re

➊

PWR
(Power)

Green

Steady

Illuminates when power is applied to the drive.

No action - no faults present

➋

STS (Status)

Green

Flashing

Drive ready, but not running & no faults are
present.

No action - no faults present

Steady

Drive running, no faults are present.

No action - no faults present

Yellow

Flashing

A type 2 (non-configurable) alarm condition
exists, drive continues to run.

A run inhibit exists. Refer to

Table 4.B

Steady

A type 1 (user configurable) alarm condition
exists, but drive continues to run.

Red

Flashing

A fault has occurred.

Refer to Table for faults.

Steady

A non-resettable fault has occurred.

Red /
Yellow

Flashing
Alternately

The drive is in flash recovery mode. The only
operation permitted is flash upgrade.

Complete Flash Upgrade

Con

trol As

se

mb

ly

Communi

cati

ons

➌

PORT

Refer to the
Communication
Adapter User
Manual

Status of DPI port internal communications (if
present).

MOD

Status of communications module (when
installed).

NET A

Status of network (if connected).

NET B

Status of secondary network (if connected).

Contro

l

➍

SYNCHLINK Green

Steady

• The module is configured as the time keeper
or

• The module is configured as a follower and

synchronization is complete.

Green

Flashing

The follower(s) are not configured with the time
keeper.

Red

Flashing

• The module is configured as a time master

on SynchLink and has received time
information from another time master on
SynchLink.

ENABLE

Green

On

The drive’s enable input is high.