Figure 1.2, 10 installation/wiring, Phase selection jumper fan voltage – Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 24

Advertising
background image

1-10

Installation/Wiring

Figure 1.2 Frames 5 & 6 Jumper and Transformer Locations (Frame 5 shown)

Frame 6 Transformer Tap Access

The transformer is located behind the Power Terminal Block in the area
shown in

Figure 1.2

. Gain access by releasing the terminal block from the

rail. To release terminal block and change tap:

1. Locate the small metal tab at the bottom of the end block.

2. Press the tab in and pull the top of the block out. Repeat for next block if

desired.

3. Select appropriate transformer tap.

4. Replace block(s) in reverse order.

Important Common Bus (DC Input) Application Notes

1. If drives without internal precharge are used (Frames 5 & 6 only), then:

a) precharge capability must be provided in the system to guard against

possible damage, and

2. disconnect switches Must Not be used between the input of the drive and

a common DC bus without the use of an external precharge device.

WIRE RANGE: 14-1/0 AWG (2.5-35 MM

2

)

TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY

POWER TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (16-35 MM

2

)

TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM

2

)

TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

17

21

INPUT AC

OUTPUT

Optional

Communications

Module

9

LINE
TYPE

SPARE 1

SPARE 2

3-PH 1-PH

480 Volt Tap

600 Volt Tap

690 Volt Tap

400 Volt Tap

Phase Selection
Jumper

Fan Voltage