Channel B Remote I/O Input 7

[ChB RIOA In 7]

–– adapter mode

[ChB RIOS In 7]

–– scanner mode

ChB RIOx In 7 contains the eighth word or data
group from the PLC controller output image table.
The RIO scanner transfers the data to the drive
every rack scan. The PLC Communications Adapter
Board can use this value directly. Other drive
functions can use this value through a configuration
link.

Parameter Number

337➀

Parameter Type

Read Only, Source

Display Units / Drive Units

None

Factory Default

None

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communications I/O – Channel B

➀ This parameter is not available if you set up channel B for DH+. Availability also
depends on the selected rack size.

Note: All eight words are displayed regardless of the rack size. Only the number of words corresponding to the rack size and protocol
(with or without block transfer) are functional.

338

SCANport Analog Input

[SP Analog In]

SP Analog In converts a +10V analog input value to
a +32767 value. You can then link this digital value
to one of the 1336 FORCE input parameters.

Parameter Number

338

Parameter Type

Read Only, Sink

Display Units / Drive Units

None

Factory Default

None

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communications I/O – Analog Input

339

Analog Input 1

[Analog In 1]

Analog In 1 displays the result of converting a

±

10V

signal to a

±

32767 value using Analog In 1 Scale

(parameter 393) and Analog In 1 Offset (parameter
392). You can link this digital value to other 1336
FORCE parameters.

Parameter Number

339

Parameter Type

Read Only, Source

Display Units / Drive Units

None

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communications I/O – Analog Input

340

Analog Input 2

[Analog In 2]

Analog In 2 displays the result of converting a

±

10V

signal to a

±

32767 value using Analog In 2 Scale

(parameter 395) and Analog In 2 Offset (parameter
394). You can link this digital value to other 1336
FORCE parameters.

Parameter Number

340

Parameter Type

Read Only, Source

Display Units / Drive Units

None

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communications I/O – Analog Input

341

Analog Input 3

[Analog In 3]

Analog In 3 displays the result of converting a

±

10V

signal to a

±

32767 value using Analog In 3 Scale

(parameter 397) and Analog In 3 Offset (parameter
396). You can link this digital value to other 1336
FORCE parameters.

Parameter Number

341

Parameter Type

Read Only, Source

Display Units / Drive Units

None

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communications I/O – Analog Input

Advertising