Run file data – Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual

Page 217

Advertising
background image

7–71

Publication 1336 FORCE–5.13 –– September, 1998

The following are the valid trend numbers:

This

number:

Specifies that the command is to be sent for:

4096

Trend 1

8192

Trend 2

12228

Trend 3

16384

Trend 4

The offset specifies where in the buffer you want to start reading the
32 data points. For example, if you specify an offset of 64, the Run
File Data function returns the 32 data samples starting from data
sample 64.

If you specify an offset of zero, then the BTR message has the
following format:

Header

Word 1

Header

Word 2

Header

Word 3

Trend Number

PLC Decimal Value

4100 –– Message OK

–28668 –– Message Error

Message Length

35

Drive Response –– Block Transfer Read

Data

Word 9

Data Sample 1

Data

Word 10

Data Sample 2

Data

Word 34

Data Sample 26

Data

Word 35

Data Sample 27


Timestamp

2ms Ticks

Timestamp

Seconds

Timestamp

Minutes

Timestamp

Hours

Data

Word 5

Data

Word 6

Data

Word 7

Data

Word 8

Data

Word 4

Index

Run File Data

(continued)