6–45

Publication 1336 FORCE–5.13 –– September, 1998

439

Channel B Warning Status

[ChB Warn Sts]

ChB Warn Sts lists the current warning conditions at
channel B of the PLC Communications Adapter
Board. This is only present if channel B is defined to
be either RIO adapter or RIO scanner.

Parameter Number

439

Parameter Type

Read Only, Source

Display Units / Drive Units

Bits

Factory Default

0

Minimum Value

0

Maximum Value

7 (adapter) or 15 (scanner)

File – Group

Diagnostics – Fault Select/Status

Communications I/O – Fault Select/Status

When RIO adapter is used:
Enums

Bit 2 Bit 1 Bit 0

Enums

Warning

Res/Pgm/Test

ChB Res/Pgm/Test (Flt 36024)

Comm Loss

ChB Comm Loss (Flt 36022)

Rack Inhibit

Rack Inhibit (Flt 36025)

When RIO scanner is used:
Enums

Bit 3 Bit 2 Bit 1 Bit 0

Enums

Warning

Rck Flt Grp0

ChB G0 Rack Flt (Flt 36031)

Rck Flt Grp2

ChB G2 Rack Flt (Flt 36032)

Rck Flt Grp4

ChB G4 Rack Flt (Flt 36033)

Rck Flt Grp6

ChB G6 Rack Flt (Flt 36034)

440

SCANport Fault Selection

[SP Fault Sel]

SP Fault Sel indicates which ports will cause a drive
soft fault on loss of communications.

Parameter Number

440

Parameter Type

Read Only, Source

Display Units / Drive Units

Bits

Factory Default

0011

1110

Minimum Value

0000

0000

Maximum Value

0011

1110

File – Group

Diagnostics – Fault Select/Status

Communications I/O – Fault Select/Status

Enums
Bit 5 Bit 4 Bit 3 Bit 2 Bit 1

Enums

Fault

Port 1

SP Pt1 Timeout (Flt 26038)

Port 2

SP Pt2 Timeout (Flt 26039)

Port 3

SP Pt3 Timeout (Flt 26040)

Port 4

SP Pt4 Timeout (Flt 26041)

Port 5

SP Pt5 Timeout (Flt 26042)

441

SCANport Warning Selection

[SP Warn Sel]

SP Warn Sel indicates which ports will cause a drive
warning on loss of communications.

Parameter Number

441

Parameter Type

Read Only, Source

Display Units / Drive Units

Bits

Factory Default

0011

1110

Minimum Value

0000

0000

Maximum Value

0011

1110

File – Group

Diagnostics – Fault Select/Status

Communications I/O – Fault Select/Status

Enums
Bit 5 Bit 4 Bit 3 Bit 2 Bit 1

Enums

Warning

Port 1

SP Pt1 Timeout (Flt 26038)

Port 2

SP Pt2 Timeout (Flt 26039)

Port 3

SP Pt3 Timeout (Flt 26040)

Port 4

SP Pt4 Timeout (Flt 26041)

Port 5

SP Pt5 Timeout (Flt 26042)

Advertising