Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual

Page 71

Advertising
background image

4–5

Publication 1336 FORCE–5.13 –– September, 1998

Communication Command:

PLC-5 TYPED READ

PLC-5 Data Table Address:

N20:0

Ignore if timed-out:

0 TO

Size in Elements:

10

to be retried:

0 NR

Local/Remote:

LOCAL

awaiting execution:

0 EW

Remote Station:

N/A

continuous:

0 CO

Link ID:

N/A

error:

0 ER

Remote Link Type:

N/A

message done:

0 DN

Local Node Address:

11

message transmitting:

0 ST

Destination Data Table Address:

N10:100

message enabled:

0 EN

control bit addr: N7:0/15

ERROR CODE:

0 (DEC)

BLOCK SIZE = 9 WORDS

Press a function key to change a value.
>[
Rem Prog Forces: None

Data: Formatted

5/10 File Temp

Size in

Toggle

Elements

Bit

MESSAGE INSTRUCTION DATA MONITOR FOR CONTROL BLOCK N7:0

Rung 2:0
This rung will read parameters 100-109 when bit B3/0 is toggled from zero to one. The parameter information is stored in N20: 0-9 in this PLC. The
drive DH+ station ID is 11.

(EN)

(DN)

(ER)

0

Enable Message Command
to Drive 1
B3

Drive 1
Parameter Read

MSG

SEND/REC MESSAGE
Control Block N7:0