Setting Your Protocol
Use the following chart to set switches 1 and 2 on either U2 or U4 to
specify your protocol.
If you are using:
Then set SW1
to:
And SW2 to:
RIO without block transfer
Off
Off
RIO with block transfer
Off
On
DH+
On
Off
RIO scanner mode
On
On
Setting Your Baud Rate
Use the following chart to set switches 3 and 4 on either U2 or U4 to
specify the baud rate that you want to use.
If you want to
communicate at:
Then set
SW3 to:
And SW4 to:
57.6K
Off
Off
115.2K
Off
On
230.4K
On
Off/On
Once you have set the protocol and baud rate DIP switches, you
should go to the section appropriate to your protocol:
If you selected this protocol:
Go to this page:
RIO with or without block transfer
Page 2–3
DH+
Page 2–8
RIO scanner mode
Page 2–6
ON =
OFF =
U2 or U4
Switches 1 and 2
1
2
3
4
5
6
7
8
0
N
0N C
HA
NN
EL A
HIG
H
U2
1
2
3
4
5
6
7
8
0
N
0N C
HA
NN
EL B
HIG
H
U4
RIO without
Block Transfer
RIO with
Block Transfer
DH+
RIO Scanner
SW1
Off
Off
On
On
SW2
Off
On
Off
On
ON =
OFF =
U2 or U4
Switches 3 and 4
1
2
3
4
5
6
7
8
0
N
0N C
HA
NN
EL A
HIG
H
U2
1
2
3
4
5
6
7
8
0
N
0N C
HA
NN
EL B
HIG
H
U4
Baud Rate
57.6K
115.2K
230.4K
230.4K
SW3
Off
Off
On
On
SW4
Off
On
Off
On